Siemens QFA3100 Installation Instructions Manual Download Page 1

 

 

Installation Instructions 

Document No. 129-416 

October 5, 2009 

 

Q-Series Outdoor Air Relative Humidity 
and Relative Humidity & Temperature 
Sensors 

 

 

Item Number 129-416, Rev. BA

 

Page 1 of 2 

Product Description 

The Q-Series Outdoor Air Relative Humidity, and 
Relative Humidity & Temperature Sensors monitor 
and transmit changes in humidity and temperature to 
the building control systems. These units are 
especially suited for applications where precise, 
stable humidity sensing is required. Standard 
models available are 2% and 2% certified, for both 
humidity only and combination humidity with 
temperature sensing. Sensors are offered with either 
4 to 20 mA or 0 to 10 Volt output signals. 

Product Numbers 

Part Number 

Description 

QFA3100 

Outdoor air humidity sensor (2%),  
0 to 10 Vdc 

QFA3101 

Outdoor air humidity sensor (2%),  
4 to 20 mA 

QFA3160 

Outdoor air humidity sensor (2%),  
0 to 10 Vdc/Temp 0 to 10 Vdc 

QFA3160D 

Outdoor air humidity sensor (2%),  
0 to 10 Vdc/Temp 0 to 10 Vdc with 
display 

QFA3171 

Outdoor air humidity sensor (2%),  
4 to 20 mA/Temp 4 to 20 mA 

QFA3171D 

Outdoor air humidity sensor (2%),  
4 to 20 mA/Temp 4 to 20 mA with 
display 

QFA4171 

Outdoor air humidity sensor (2%),  
4 to 20 mA/Temp 4 to 20 mA, certified 

QFA4171D 

Outdoor air humidity sensor (2%),  
4 to 20 mA/Temp 4 to 20 mA, certified 
with display 

QFA4160 

Outdoor air humidity sensor (2%),  
0 t 10 Vdc/Temp 0 to 10 Vdc, certified 

QFA4160D 

Outdoor air humidity sensor (2%),  
0 t 10 Vdc/Temp 0 to 10 Vdc, certified 
with display 

Accessories 

AQF3101 

Sensor filter cap 

AQF4150 

Replaceable, certified sensor tip 

AQF3100 

Sun shield 

74 662 0104 0 

US 1/2-inch rigid conduit adapter 

Required Tools 

 

Phillips screwdrivers, sizes No. 1 and No. 2 

 

Medium flat-blade screwdriver 

 

Wire cutters/strippers 

 

Tape measure 

 

Medium-duty electric drill 

 

Drill bit for wall anchor hole 

 

Marker or pencil 

 

Two No. 10 screws and wall anchors 

Expected Installation Time 

30 minutes 

Prerequisites 

 

Ensure that the appropriate field wiring is 
installed. 

Appropriate wiring is one or more twisted pair or 
three conductor cables (plenum or non-plenum 
as required) within the maximum wiring run 
length for the humidity/temperature controller. 
The maximum recommended length is 750 feet 
(229 m). 

 

Ensure that all wiring complies with National 
Electric Code (NEC) and local regulations. 

Installation 

1.  Determine where the sensor is to be located and 

install the Sun Shield, AQF3100, as shown in 
Figure 1. The installation surface determines 
which mounting components are to be used. 

NOTE: 

The shield must be mounted vertically 
as shown in Figure 1. 

2.  Remove sensor cover and install plug in 

knockout next to sensing probe. See  
Figure 1 (2). 

3.  Pull the field wiring through the conduit and into 

the sensor base. See Figure 2. 