Siemens QAA4292.EWSC Installation Instructions Download Page 1

 
 

 

 

Installation Instructions 

Document No. A6V11521281 

February 20, 2019 

 

Series 4292 Wireless Sensor System 
Sensors 

 

 

Page 1 of 5 

Product Description 

These wireless sensors are used within the Series 
4292 wireless system architecture to gather room 
environmental data and transmit it to the system 
gateway for export to the building automation 
system. 

NOTE: 

These sensors are for use with the Siemens 
4292 Wireless Sensing System and are not 
compatible with other wireless networks. 

Model Number 

Description 

QAA4292.EWSC** 

Room Temperature Sensor 

QFA4292.EWSC** 

Room RH & Temperature Sensor 

QPA4292.EWSC** 

Room CO

2

 sensor 

563-083** 

Dry Contact Closure Transmitter 

563-084* 

BACnet/IP Gateway 

563-085* 

Wireless Repeater 

535-104 

24V Power Supply 

563-087* 

BACnet/MSTP Gateway 

563-088* 

Modbus RTU/TCP Gateway 

563-089** 

Site Survey Tool 

* Class A device 
** Class B device 

Expected Installation Time 

25 minutes 

Prerequisites 

 

Familiarity with the Siemens 4292 Wireless 
Sensor System 

– See 

Series 4292 Wireless 

Sensor System User Guide

  

P/N A6V11544782 

 

Thoroughly review these instructions before 
beginning. 

 

 

 

QAA4292.EWSC 

QFA4292.EWSC 

563-083 

QPA4292.EWSC 

 

 

Series 4292 

Gateway/Repeater 

Site Survey Tool 

. Required Tools 

 

Series 4292 Gateway 

 

USB-A to USB-Mini cable (supplied with 
Gateway) 

 

Series 4292 Site Survey Tool (Siemens part 
number 563-089) 

 

Basic hand tools 

 

1 mm flatblade screwdriver (QAA4292.EWSC 
and 563-083) 

Related Documentation 

 

A6V11536846: 

Series 4292 Wireless Sensor System 

Technical Specification Sheet

 

 

A6V11541947: 

Series 4292 Wireless Sensor System 

Site Survey Tool Operating Instructions

 

 

A6V11544782:

 Series 4292 Wireless Sensor System 

User Guide 

 

Field Server Protocol Driver Sheet BACnet PIC 
Statement

 

 

 
 

 

 

Summary of Contents for QAA4292.EWSC

Page 1: ...Cnet MSTP Gateway 563 088 Modbus RTU TCP Gateway 563 089 Site Survey Tool Class A device Class B device Expected Installation Time 25 minutes Prerequisites Familiarity with the Siemens 4292 Wireless Sensor System See Series 4292 Wireless Sensor System User Guide P N A6V11544782 Thoroughly review these instructions before beginning QAA4292 EWSC QFA4292 EWSC 563 083 QPA4292 EWSC Series 4292 Gateway ...

Page 2: ...at one time NOTE The gateway must be configured to communicate with a terminal emulator per Series 4292 Wireless Sensor System User Guide Document No A6V11544782 before attempting to configure sensors 1 Using the terminal emulator function select S from the main menu 2 Attach the sensor to the gateway using the USB cable supplied with the gateway On the QPA4292 EWSC CO2 sensor the cover must be re...

Page 3: ...ontinuing to transmit data over the network Configure the new sensor 1 Connect the new sensor to the gateway using the PC Interface port 2 Select S Configure Sensor in Gateway 3 Record the SENSOR ID as shown on screen 4 Disconnect the sensor from the gateway and install in the desired location QAA4292 EWSC Remote Temperature Sensor Wiring In addition to the onboard temperature sensor the QAA4292 E...

Page 4: ...ically return to outdoor background levels while the building is vacant If manual calibration is required place the sensor outside or in a location with a background concentration of CO2 near 385 ppm Press the Cal RESET button on the inside of the sensor for two seconds The sensor should remain in this location for 30 minutes NOTE When placing the sensor outside for calibration ensure that it is n...

Page 5: ...n outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Class A Devices Statement Note This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when ...