Safety, approvals, EMC
7.2 Test voltage
SITOP PSU300M/300B
60
Manual, 11.2014, C98130-A7574-A2-2-7629
7.2
Test voltage
Figure 7-1
Test voltage without auxiliary contact diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
●
Connect the input terminals with one another
●
Connect the output terminals and PE together
Test (C)
●
Connect the output terminals with one another and measure with respect to PE
Table 7- 1
Test voltage
Test time
Prim
↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 VDC
2200 VDC
700 VDC
60 s
3000 VAC
1500 VAC
500 VAC
Production test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Field test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA