relay transfers if the local alarm default signal is
activated by an initiating control board (CZM-4 or
ALD-2I). This occurs when the initiating board
cannot communicate with the MXL. Likewise, if any
local module, including the PSR-1, loses communi-
cation with the MXL, the trouble relay transfers.
When the system is operating normally, these relays
are controlled by output logic only. See Figure 6 for
ratings and wiring instruction.

Auxiliary Power for CZM-1 and PS-5A (TB3)

A Class A power limited output is provided on TB3,
terminals 3-6 for use with the CZM-1 and PS-5A.

1. This power is available on TB3, terminals 3

through 6.

2. All wiring must be in accordance with Article

760 of NEC or local building codes.

3. The power for CZM-1 and PS-5A is power

limited to NFPA 70 per NEC 760.

4. Electrical Ratings:

18-31 VDC, unfiltered full wave
2A max

5. You may connect a maximum of 40 CZM-1s

to the TB3 power source. Follow the guide-
lines below when wiring.

a. This power may be wired Class A, as

shown in Figure 7. Class A wiring can
support a maximum of 20 CZM-1s, with

total line resistance of 4 ohms max.

T-tapping is not allowed.

b. Refer to Figure 8. Class B wiring can be

used

to obtain the maximum of 40 CZM-1s.

 Each

Class B wire run can support a maximum of

Figure 6

Common Alarm and Common Trouble Relays

Figure 7

CZM-1 Power, Class A Wiring

6

5

4

3

2

1

TB1

COMMON

TROUBLE

RATINGS

2A, 30 VDC

RESISTIVE

COMMON

ALARM

REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ

AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR

HIGHER, FOR FURTHER INFORMATION.

6

5

4

2

3

1

+

+

_
_

TB3

CZM-1

NO

T-TAPPING ALLOWED

CLASS A WIRING

REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ

AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR

HIGHER, FOR FURTHER INFORMATION.

18-31 VDC

2A MAX

POWER LIMITED TO

NFPA 70 PER NEC 760

4 OHMS MAX (TOTAL)

18 AWG MIN
POSITIVE AND NEGATIVE

GROUND FAULT DETECTED

AT <30K OHMS FOR TB3, 1-6

RES EOL ASSEMBLY

120 OHMS, 1/4W, 5%

P/N 140-049099

MMB-3

4
3
2
1

CHASSIS

NO

EOLR

TB1

TB1

TB4

4
3
2
1

PSR-1

MOI-7

PSR-1

TB4

4
3
2
1

4 3 2 1

RES EOL ASSEMBLY

120 OHMS, 1/4W, 5%

P/N 140-049099

NO

EOLR

SHIELD

N

E

T

-

7

RES EOL ASSEMBLY

120 OHMS, 1/4W, 5%

P/N 140-049099

NET-7

OR

NET-7M

Figure 5

Connecting a Style 7 Network to MMB-3

REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV
SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR
ADDITIONAL WIRING INFORMATION.

SET "MMB-3 MNET STYLE 7" TO "YES" IN THE CSGM.

Summary of Contents for PSR-1

Page 1: ...s an interface between remote option modules and the MXL when used with a NET 4 plug in communica tion module See Instructions P N 315 090909 or NET 7 plug in communication module See Instructions P N 315 091914 The PSR 1 can also be used to power an MOI MOD annunciator driver set In addition the PSR 1 can be used as an auxiliary power supply in a standalone mode without an MXL The PSR 1 has LED s...

Page 2: ...l Standby 24 VDC Module Current 3 Total the right hand column and record it at the bottom of the form opposite Total System Current 4 For NFPA 72 Local and 72 Proprietary systems multiply the total system current by 24 and record it at that Total AH location or For NFPA 72 Municipal Tie and 72 Remote Station systems multiply the total system current by 60 and record it at that Total AH location or...

Page 3: ...O M A m 2 0 0 7 I O M A m 0 2 0 0 4 T E N A m 5 0 0 7 T E N A m 0 3 0 0 M 7 T E N A m 0 3 0 0 W 1 M I N A m 0 6 0 0 W 1 M I N M 1 M I N h t i w A m 0 3 1 0 0 1 C C O A m 5 1 0 0 1 L A P 2 e t o N e e S 0 0 1 M I P A m 5 1 0 0 2 M I P 2 e t o N e e S 0 0 A 5 S P d a o l V 5 f o A m 0 1 0 0 7 N 5 S P d a o l V 5 f o A m 5 4 0 0 2 F 1 1 C C R 1 E S R R 2 f i A m 5 1 A m 5 5 d e s u s i 1 M I P 0 0 C ...

Page 4: ... l e r A m 0 1 4 M S C x a m A 5 1 A m 0 7 t i u c r i c r e p A m 0 1 6 B 1 1 M Z C A m 0 5 0 0 4 M Z C A m 5 6 7 m r a l a n i s e n o z 4 A m 0 1 P C 0 0 3 2 D 0 0 A m 0 0 2 E 1 1 T C D A m 0 9 1 0 0 1 C M D 0 0 A m 0 2 6 B 1 1 P C I d a o l e c i v e d A 0 1 x a m A 5 1 0 0 T C A D M A m 0 6 2 0 0 6 1 D I M x a m A m 8 4 A m 2 4 2 B K M 0 0 A m 5 7 C 5 B K M A m 0 0 3 0 0 C 6 6 B K M A m 0 0 3...

Page 5: ...r BATTERY VOLTAGE THRESHOLDS Battery Status Conditions Battery Voltage Volts Battery Not Installed 14 0 Charger Disabled 18 3 Battery Low Fault On Battery 21 0 Battery Low Fault On AC 24 0 Battery High Fault 30 0 Security Mode UL 1076 Operation S2 5 To Disable the Tamper Switch The PSR 1 does not support the use of security points from initiating circuits in its enclosure To disable the tamper swi...

Page 6: ... X O O X X O X X X O X X X O X X X O O O O X X X X O X O O X X X X O O X O X X X X O X X O X X X X O O O X X X X X O X O X X X X X O O X X X X X X O X X X X X X X O 8 2 1 9 2 1 0 3 1 1 3 1 2 3 1 3 3 1 4 3 1 5 3 1 6 3 1 7 3 1 8 3 1 9 3 1 0 4 1 1 4 1 2 4 1 3 4 1 4 4 1 5 4 1 6 4 1 7 4 1 8 4 1 9 4 1 0 5 1 1 5 1 2 5 1 3 5 1 4 5 1 5 5 1 6 5 1 7 5 1 8 5 1 9 5 1 0 6 1 1 6 1 2 6 1 3 6 1 4 6 1 5 6 1 6 6 1 7...

Page 7: ...HE NETWORK CONNECTION TB4 For the PSR 1 to communicate with the MXL a NET 4 or NET 7 network interface card must be installed into P7 of the PSR 1 For a NET 4 con Figure 3 Mounting the PSR 1 on the MBR MP nect the MXL network MMB to terminals 1 and 2 of TB4 as indicated in Figure 4 Terminate the shield at the MMB only For a NET 7 refer to Figure 2 of the NET 7 Installation Instructions P N 315 091...

Page 8: ...f 4 ohms max T tapping is not allowed b Refer to Figure 8 Class B wiring can be used to obtain the maximum of 40 CZM 1s Each Class B wire run can support a maximum of Figure 6 Common Alarm and Common Trouble Relays Figure 7 CZM 1 Power Class A Wiring 6 5 4 3 2 1 TB1 COMMON TROUBLE RATINGS 2A 30 VDC RESISTIVE COMMON ALARM REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 ...

Page 9: ...ual Class B power runs for a total of 40 devices for example 12 8 6 and 14 CZM 1s with each of the four runs not exceeding 4 ohms resistance T tapping is allowed provided the total resis tance of all wires does not exceed 4 ohms 6 Refer to Figures 9 and 10 for wiring instruc tions for the PS 5A MOI 7 Power P9 The PSR 1 may be used in standalone mode as the power supply for the MOI 7 In this config...

Page 10: ...is provided on TB3 for the MOM 4 card cage This output is rated at 6 amps MPS 6 or 12 amps MPS 12 18 31 VDC This capacity must be derated by the current drawn by the CZM 1 and PS 5A power output If the full 2 amp capacity of the CZM 1 and PS 5A output is used the MOM 4 power must be derated to 4 amps MPS 6 or 10 amps MPS 12 See Figure 13 for wiring instruc tions When a PSR 1 is used with an MKB 2 ...

Page 11: ...onnect as shown in Figure 16 Figure 14 Connecting a NET 7 in a MOM 4 REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 REVISION 6 OR HIGHER FOR ADDITIONAL WIRING INFORMATION REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 REVISION 6 OR HIGHER FOR ADDITIONAL WIRING INFORMATION REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 3...

Page 12: ...ting OMM 1s and MOM 4s with a PSR 1 REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 REVISION 6 OR HIGHER FOR ADDITIONAL WIRING INFORMA TION POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT 30K OHMS FOR TB3 1 6 ...

Reviews: