Page 74
Pointek CLS500 – INSTRUCTION MANUA
7ML19985GG03
mmmmm
Appendix A
Upper Threshold Delay
(solid-state output)
The Upper Threshold Delay controls the Activation delay: the amount of time that has to
pass uninterrupted with the probe covered to a level above the Upper Threshold Setting
before the timer expires. After the timer expires, the output signal will comply to the
setting from Menu 18 for a covered probe. Whenever the level drops below the Upper
Threshold Setting before the timer expires, the timer is restarted.
When the solid-state switch control (Menu 17) is disabled, menu 13 displays - - - -. When
the solid-state switch control is enabled, menu 13 displays the Activation delay in
seconds. As an extra identifier, an upward running d is displayed to the right of the value.
First select the solid-state switch output at menu 17 (contact open or contact closed).
1. Set the rotary switch to 3.
2. Press the RED (+) or BLUE (–) button to increase or decrease the value.
or: Press and hold a button to start a repeat function.
or: Press both buttons simultaneously to toggle the value between minimum (0)
and maximum (100).
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Identifier
Des-
cription
Values
13
17
3
On
Solid-state
switch
control
enabled
*
Upward
running d at
right of value
Upper
Threshold
Delay
Range: 0
to 100
(seconds)
factory setting
0.0
Solid-state
switch
control
disabled
Display
shows
- - - -