7.15
Diagnostics for the Route Control stations
Overview
Diagnostics for
Diagnostics tool
Called with
Operating capability of all
SIMATIC Route Control
components and communication
connections
The maintenance station is an operator station that is
specially configured for use in diagnostics.
The maintenance station has to be configured.
Additional information is available in the
documentation
Process Control System PCS 7;
Maintenance Station
Status of redundant servers
Status icons in the Route Control
Taskbar
Established connections to
SIMATIC stations
NetPro: Online view > Select CPU: PLC > Activate
Connection Status
7.16
Diagnostics for time of day
Overview
Diagnostics for
Diagnostics tool
Called with
AS-CPU time
SIMATIC Manager (Page 109) Select CPU: PLC > Set Time of Day
AS-CPU time
Module Information (Page 112) Station > Open Online
Select CPU: PLC > Set Time of Day
PC time
Control Panel > Date/Time. Do not change these
settings.
Activated time services
Windows System Utilities
Control Panel > Administrative Tools > Services
Select "Windows Time": Action > Properties
"General" tab > Startup type: ...
Synchronization status on the terminal
bus
Set PG/PC Interface (Page 94) In the Siemens SIMATIC programs Start menu:
SIMATIC NET > Set PG/PC Interface
Select interface > Click "Diagnostics" > In the
"Time" group
Configuration of time displayed in
operator control and monitoring systems
WinCC Editor "Time
Synchronization"
Open WinCC Explorer with the menu command
Editors > Time Synchronization > Open
Diagnostics in PCS 7
7.16 Diagnostics for time of day
Service support and diagnostics (V8.0)
86
Service Manual, 03/2012, A5E02779775-02