Firmware update for SIMATIC stations with redundant interface modules
Note
You can perform a firmware update of the interface modules for SIMATIC 400H station with
redundant interface modules during runtime.
3.3.4.2
How to perform a firmware update of an interface module (IM)
Introduction
This section provides a description of the update of the firmware for interface modules
(Interface Module (IM)) via Industrial Ethernet.
Requirements
The following is required to perform the update via Industrial Ethernet:
● STEP 7 V5.3 or higher is installed on the programming device or PC.
● The update file for the firmware update is available on the programming device / PC.
● The CP 443-1 is routing-capable (check in HW Config: Properties of the CP > brief
description "Routing" is listed).
● The files containing the current (new) version of the firmware is available in the file system
of your programming device or PC.
● The IM has been integrated in your PCS 7 project.
Procedure
1. Open SIMATIC Manager.
2. In the component view, select the SIMATIC station in which the IM is located.
3. Double-click the "Hardware" object in the detail window.
HW Config opens.
4. Select the IM whose firmware you want to update.
5. Select the menu command PLC > Update Firmware.
The "Update Firmware" dialog box opens.
6. Make the settings in accordance with the table below.
7. Click "Execute". The firmware is updated.