background image

11-D-1023-01 REV. 0

SMSKHCP for Main Mounting

Power Panel Kit (P5)

Type SENTRON HCP SWITCH

 

This device/system may only be set up and used in conjunction with these instructions.  Installation,  mainte-
nance  and  operation  of  this  device/system  may  only  be  performed  by  qualified  personnel.   

qualified  personnel.    Within  the 

context of these instructions,  qualified persons are defined as persons who have the skills and knowledge 
related to the construction  and operation of the electrical equipment and installations and have received 
safety training to recognize and avoid the hazards involved.  

8.

Reference fig. 7 and 8 - Installing switch.

Note: The HCP switch ships as a branch device with 

          lugs located on the load end of the switch.

          To make switch a Main device, remove lugs from

           load side and install lugs on line side of switch and

           torque bolts to the values specified on the switch.

Position the switch so that the load side connectors are above

and below the stab and the holes are aligned. Using the 5/16-18

hex head bolts (item 9), the 5/16” lock washers (item 16) and the

5/16” flat washers (item 10) attach the switch to the connectors 

using the inserts (item 24). Do not tighten. Repeat steps for all 

phases. Attach switch to support (item 12) using the two 1/4-20 X

1” machine screws (item 2) through the line side of the switch and 

into the support. Tighten screws. Tighten and torque the 5/16-18 

bolts (item 9) to values shown on rear of deadfront.

Figure 7

9

16

10

24

Figure 8

2

12

Reference fig. 9 - Installing ground assembly.

Orient the ring terminal on one end of the ground

assembly (item 11) over the 0.171” hole in the switch

main bracket (item 14). Orient the other ring terminal

on the ground assembly over the 0.171” hole in the

switch. Insert one 10-32 X 1/4” screw (item 4) 

through the ring terminal and into the 0.171” hole in

the switch main bracket and tighten.  Insert one 

10-32 X 1/4” screw through the ring terminal and 

into the 0.171” hole in the switch and tighten.

9.

Re-install the deadfront and gutter covers. 

10.

Figure 9

14

4

11

SWITCH
STAB

Reviews: