75/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Communication via zone addresses
30.08.2007
7.3.2
RXB/RXL room controllers
•
In ACS Service
Applications > Parameter settings
, open the menu tree of the
RXB/RXL room controller for which the zone address is to be set.
•
Double-click the menu line "Communication" to open the operating page, and
select the zone for which the address is to be set. Double-click to open the
dialog box for entry of the address.
•
Enter the zone address and click
OK
to confirm the value entered.
7.3.3 Zone
addressing
with
the QAX34.3 room unit
With the RXB/RXL room controllers, the zone addresses can also be set with the
QAX34.3 room unit (Minor parameterization, see section 5.6.1).
P008 Geographical zone (apartment)
1…126 -1 = Default value
P009 Geographical zone (room)
0…63
1 = Default value
P010 Geographical zone (subzone)
0…15
1 = Default value
P011 Time-switch zone (apartment)
1…126
1 = Default value
P012 Time-switch zone (room)
0…63
1 = Default value
P013 Time-switch zone (subzone)
0…15
1 = Default value
P014 Heat distribution zone, air heater
1…31
-1 = Default value
P015 Refrig distrib. zone, cooling coil
1…31
-1 = Default value
P016 Heat distr zone heating surface.
1…31
-1 = Default value
P017 Refrig distr zone cooling surface
1…31
-1 = Default value
P018 Outside temperature zone
1…31
1 = Default value
P023 Master/slave zone (group)
1…126
1 = Default value
P023 Master/slave zone (room)
0…63
-1 = Default value
P024 Master/slave zone (subzone)
0…15
1 = Default value
"P008" indicates that the "Geographical zone (apartment)" in the RXB/RXL room
controllers is parameter no. 008. For more information, refer to document
CM110385.
For the RM… controllers, the default value in the QAX34.3 room unit is "-1" rather
than "----". Both default values indicate that the zone is "out of service" and that no
process values are transmitted within the zone.
Minor parameterization
Parameter numbers and
associated zones
Notes