Trend functions
2015-10-12
You can send a test e-mail to the receiver to ensure the settings are correct.
1. Click
Test receiver
or the red pencil symbol .
2. In the
Edit
window, select the
Trigger
option.
3. Confirm with
OK
.
OZW sends a test e-mail to the entered receiver and confirms the
transmission under the data point
Trend data sent
with
Yes
.
If transmission failed, a possible cause is provided under
Reason
, see
Section 2.7, Functional check, "Test message receiver".
4. Check whether the e-mail arrived at the receiver.
E-mail receiver settings are retained when deleting or overwriting an existing trend
definition.
9.3.2 Sent transmission options per trend channel
The transmit interval can be set separately for each trend channel 1…5.
1. In secondary navigation, select desired
Trend channel 1…5
.
The window displays name, state, circular logging, transmit interval, and
message receiver.
1. Click
Transmit interval
or click the red pencil
.
The edit window opens.
Send test e-mail to
receiver
Note
Set transmit interval