2.7 Functional
check
Connections must be tested if all settings were made to the Web Server as well as
to system devices.
A PC on the local network is used to test operations via LAN. The log in dialog
box must be displayed after entering the local IP address for the Web Server
(see Section 2.2.2).
We recommend using mobile participants with Internet access (Smart phone,
mobile phone) to test operation over the Internet.
After registration, log in, and activating the plant, access via the portal must be
possible (see Section 3.1 "Set up access via portal").
The log in dialog box displays after entering the public IP address of plant domain
(see Section 4," Operate using a web browser").
Do the test if the Web Server is to send a message or system report via e-mail
for a fault.
The test is also carried out if message suppression is switched on.
Path: Home > 0.5 OZW672… > Settings > Message receiver
Data point
Explanation, example
Test message receiver
Default val:
---
Setting val: Message receiver
1..4
Select a message receiver to test the
connection to the receiver.
—
System report sent
Display values: ---, Yes, No
The display changes from "
---
" to "Yes" after a
few seconds. Message sent successfully.
No: Message receiver not reached.
—
Cause
Display values:
---, Network cable, DNS setting,
Address mail server, Port number
mail server, E-mail address
receiver, Authentication mail
server. See the following table.
"Cause" displays the results of "System
report sent".
For "Yes" the cause is "---"
For "No" the cause is displayed.
The first fault is displayed for multiple faults.
—
Message inhibition
Display values: Yes, No
Shows the message suppression switch
setting (
8
) (see Section 1.2).
—
Test condition
LAN
Internet
Access via portal
Access without portal
Test message receiver
Note