Planning
Fire detection
4
62 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
4.2.7 Setting the parameter set in collective operation
In the case of the point detector OOH740, the set parameter set depends on the
resistor installed in the detector base.
Parameter set in fire
detector OOH740
Resistance value in the
detector base
Flashing signal to display the set parameter set in the
first three minutes following the detector line being
started up
'Standard Plus'
-
Once every 6 s
'Suppression'
33 k
Ω
(PSR720-1)
Twice every 6 s
'High Sensitive Fast'
68 k
Ω
(PSR720-2)
Three times every 8 s
If no resistor is installed in the detector base, the 'Standard Plus' parameter set is
set.
Upon commissioning of the fire detection system, the optimum parameter set must
be selected based on the existing risk and the ambient conditions.
See also
2
Internal alarm indicator in the case of ES <20 (OOH740 and
2
2
4.2.8 Sample applications for OOH740
The table below includes examples regarding the selection of the parameter set for
the point detector. The examples cannot be used universally, but illustrate typical
applications.
Environment
Deceptive phenomena / detector
behavior
Parameter set
Addressed
Collective
Normal office, room
without any particular
deceptive phenomena
No special requirements
'High
Compensation (7)'
'Standard Plus'
Possible deceptive
phenomena, e.g. electric
kettle
Vapor as deceptive phenomenon
'Balanced (4)' or
'Suppression (5)'
'Suppression'
Kitchen
A lot of vapor as deceptive
phenomenon
'Suppression (5)' or
'BS (4)'
'Suppression'
Hospital room, museum
Quick response needed, no deceptive
phenomena expected
'Fast Response (6)' 'Standard Plus'
Clean room
Fast and very sensitive reaction
required
'High Sensitive
Fast (9)'
'High Sensitive
Fast'