Installation Instructions

Document No. 565-957

August 12, 2005

Siemens MXL Driver

These installation instructions only cover the
connection of the Siemens MXL Driver to the MXL
system. For hardware installation of the Modular
Equipment Controller, see document number
565–570. For hardware installation of the Power
Open Processor, see document number 565–571.

Product Description

The Siemens MXL Driver enables communication
between the APOGEE

®

Automation System and the

MXL system.

Product Numbers

986-83379A

Siemens MXL Driver, Open Processor
with RS-485 BLN

986-83379B

Siemens MXL Driver, Open Processor
with Ethernet BLN

986-83379C

Siemens MXL Driver, MEC with
RS-485 BLN, 8DI, 8DO, 8AI, 8AO,
point expansion support, HOA-ready

986-83379D

Siemens MXL Driver, MEC with
RS-485 BLN, 8DI, 8DO, 8AI, 8AO,
point expansion support, with HOA

986-83379E

Siemens MXL Driver, MEC with
RS-485 BLN, 8DI, 8DO, 8AI, 8AO,
point expansion support, modem,
HOA-ready

986-83379F

Siemens MXL Driver, MEC with
RS-485 BLN, 8DI, 8DO, 8AI, 8AO,
point expansion support, modem, with
HOA

986-83379G

Siemens MXL Driver, MEC with
Ethernet BLN, 8DI, 8DO, 8AI, 8AO,
point expansion support, HOA-ready

986-83379H

Siemens MXL Driver, MEC with
Ethernet BLN, 8DI, 8DO, 8AI, 8AO,
point expansion support, with HOA

Warning/Caution Notations

WARNING:

Personal injury/loss of life may occur if you
do not follow the procedures as speci

fi

ed.

CAUTION:

Equipment damage or loss of data may
occur if you do not follow the procedures
as speci

fi

ed.

Expected Installation Times

7 minutes.

Required Tools and Materials

Flat-blade screwdriver (1/8-inch blade width).

Wire strippers.

Cabling and connectors. See the

Connecting

the Siemens MXL Driver to the MXL System

section.

CAUTION:

Always wear an electro-static discharge
wrist strap and discharge accumulated
static before touching

fi

eld panel

components.

Prerequisites

Driver hardware is installed according to its
respective installation instructions.

Depending on the type of installation, other
prerequisites may have to be completed.

Connecting the Siemens MXL

Driver to the MXL System

Follow these steps to connect the Siemens MXL
Driver to the MXL system:

Item Number: 565-957, Rev. 030

Page 1 of 4

Summary of Contents for MXL

Page 1: ...8DI 8DO 8AI 8AO point expansion support modem with HOA 986 83379G Siemens MXL Driver MEC with Ethernet BLN 8DI 8DO 8AI 8AO point expansion support HOA ready 986 83379H Siemens MXL Driver MEC with Ethernet BLN 8DI 8DO 8AI 8AO point expansion support with HOA Warning Caution Notations WARNING Personal injury loss of life may occur if you do not follow the procedures as specified CAUTION Equipment da...

Page 2: ... on the appropriate terminal block as specified above Terminal 1 is the negative terminal and terminal 2 is the positive terminal There is no terminal available for the shield so it will be connected at the driver See Figure 1 and Figure 2 6 Connect a 120 ohm 1 4 watt resistor between terminals 3 and 4 of this same terminal block See Figure 2 7 At the MEC MBC RBC attach the and S leads of the RS 4...

Page 3: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Do NOT use GW0955R1 Figure 2 Connecting the Siemens MXL Driver to the MXL System The standard practice used by MXL installers would also require a 120 ohm resistor between terminals 1 and 2 Do NOT install a resistor across these terminals Siemens Building Technologies Inc Page 3 of 4 ...

Page 4: ...nts are introduced Product or company names mentioned herein may be the trademarks of their respective owners 2005 Siemens Building Technologies Inc Siemens Building Technologies Inc Your feedback is important to us If you have Document No 565 957 1000 Deerfield Parkway comments about this document please send Country of Origin US Buffalo Grove IL 60089 4513 them to SBT_technical editor siemens co...

Reviews: