SITRANS P, MS series
87
C79000-B5674-C40-04
On-site Operation and Display
Adjusting the start of scale and full scale
If the output current is not set but continuously adjusted, a DC ammeter is required.
In addition the currents to be adjusted must be calculated mathematically (Chapter
3.1.2, p. 83). An adjustment can be made for the start of scale, full scale or both val-
ues one after the other.
Preparations:
1. Clean the housing so that no dirt can penetrate.
2. Unscrew the front cover (Figure 2, p. 75), remove the digital indicator (if fitted).
3. Connect the DC ammeter to the test plug (Figure 22, p. 107).
•
Adjust
start of scale
WARNING
Only certified, zum Messumformer passende, ammeters may be used in intrinsi-
cally safe circuits.
In areas with a potential explosion hazard, the housing cover of transmitters with
the type of protection "explosion-proof" may only be unscrewed when the device is
not energized. If transmitters are to be used as category 1 / 2 equipment, please
observe the EC examination certificates bzw. die für Ihr Land gültige Prüfbeschei-
nigung.
Inputs, hold times
Explanations
(1) Apply reference pressure to the
transmitter
As assumed by the calculation formula
(2) Press [Z/
↓
], hold, then [S/
↑
],
immediately, release both but-
tons
Activate start of scale adjustment Press
(3) [Z/
↓
] or [S/
↑
]
until the desired output current is set on the DC
ammeter which corresponds to the new start of
scale
(4) Press both buttons simulta-
neously and wait 2 s or auto-
matically after 2 min.
Save
Summary of Contents for MS Series
Page 2: ......
Page 4: ...SITRANS P Serie MS 4 C79000 B5674 C40 04 ...
Page 10: ...SITRANS P Serie MS 10 C79000 B5674 C40 04 ...
Page 16: ...SITRANS P Serie MS 16 C79000 B5674 C40 04 Technische Beschreibung ...
Page 50: ...SITRANS P Serie MS 50 C79000 B5674 C40 04 Inbetriebnahme ...
Page 51: ...SITRANS P Serie MS 51 C79000 B5674 C40 04 Technische Daten 7 Siehe folgende Seiten ...
Page 56: ...SITRANS P Serie MS 56 C79000 B5674 C40 04 Pflege und Wartung ...
Page 60: ...SITRANS P Serie MS 60 C79000 B5674 C40 04 Zertifikate ...
Page 66: ...SITRANS P Serie MS 66 C79000 B5674 C40 04 Index ...
Page 72: ...SITRANS P MS series 72 C79000 B5674 C40 04 ...
Page 78: ...SITRANS P MS series 78 C79000 B5674 C40 04 Technical Description ...
Page 112: ...SITRANS P MS series 112 C79000 B5674 C40 04 Commissioning ...
Page 113: ...SITRANS P MS series 113 C79000 B5674 C40 04 Technical Data 7 See following pages ...
Page 118: ...SITRANS P MS series 118 C79000 B5674 C40 04 Maintenance and Care ...
Page 122: ...SITRANS P MS series 122 C79000 B5674 C40 04 Certificates ...
Page 128: ...SITRANS P MS series 128 C79000 B5674 C40 04 Index ...
Page 129: ......