5.3
Optional Board
5.3.1
MOBY-M
6AW5458-7DB
The data carrier type and the voltage supply of the LBS must
be set.
Jumper settings:
LED H1:
BR3
BR2
BR1
BR4
X1
X2
H1
MOBY Channel 1
MOBY Channel 2
external 24 V*
BR1 Setting the DAT type
*) BR1 on motherboard is to be set to non-floating
voltage
set by software
8 byte fixed code
16 byte fixed code
64 byte slow
64 byte fast
2 Kbyte
BR2 / BR3
BR2 / BR3
BR4
internal 24 V
Command waiting
(connection to LBS is uninterrupted,
program is waiting for data carrier)
5.3.2
MOBY-I
6AW5458-7VB (without file handler)
6AW5458-7DH (with file handler)
*) BR1 on motherboard is to be set to non-floating
voltage
BR 1
Interface to SLG is TTY (currently not
available)
BR5
external 24 V
Test mode of operation; on interference,
the dialogue to the mobile data memory
will be interrupted sooner. Thus, weak
points and interference can be detected
during initial startup.
normal operation
BR2 / BR3
MOBY Channel 1
MOBY Channel 2
BR2 / BR3
interface to the SLG is RS422
BR4
internal 24 V*
BR3
BR2
BR1
BR5
BR4
X2
X1
H1
H2
H3
LED H1: RED; The last detected error is indicated as a
flashing pattern. The error indication is not
deleted until the ES 030K is switched off.
LED H2: GREEN; Indicates the presence (ANW) of an
MDS (same meaning as bit 7 of FY 16/17)
LED H3: YELLOW; Irregular flashing indicates a running
dialog to the SLG.