Installation Instructions

Model MKB-4

Annunciator/Keypad Module

P/N 315-093575-5

Fire Safety

The 

SIEMENS

 

Model

 

MKB-4 Annunciator/Keypad

provides the MXL-IQ/MXL System with its primary

control and annunciation. The MKB-4 communi-

cates with the SMB-1/2 or the MMB-1/2 Main

Control Board through the System network link.

OPERATION

The MKB-4 has an 80-character, backlit LCD

alphanumeric display that continuously updates

information about the System status and user

defined device messages (See Figure 1). If there

are multiple alarms and/or troubles that include

supervisories and security conditions, the MKB-4

displays the highest priority event that occurred.

The user can see additional alarm and trouble

data by pressing the NEXT key. Press the HOLD

key at any time to stop the display from scrolling.
There are switches for the following functions:

• Acknowledging fire alarms 

(ALARM ACK)

• Silencing audibles 

(AUD SIL)

• Acknowledging supervisories 

(SUPV ACK)

• Acknowledging troubles 

(TRBL ACK)

• Acknowledging security conditions 

(SEC ACK)

There is also a separate key for resetting the

Control Panel 

(RESET)

.

The 10-digit numeric keypad allows entry of the

three levels of user passwords. It also does

specific menu-driven operations as well as

programming and maintenance functions.
Another series of switches located on the MKB-4

allows the user access to the MXL-IQ/MXL

Control menu. There are also System status

indicator LEDs. The 

ALARM 

and 

TROUBLE

LEDs function even if the main processor fails

(See Figure 1).

Figure 1

MKB-4 Panel

12.00.00 JAN 01, 2001

SIEMENS BUILDING TECHNOLOGIES

SYSTEM

NORMAL

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

Summary of Contents for MKB-4

Page 1: ...op the display from scrolling There are switches for the following functions Acknowledging fire alarms ALARM ACK Silencing audibles AUD SIL Acknowledging supervisories SUPV ACK Acknowledging troubles TRBL ACK Acknowledging security conditions SEC ACK There is also a separate key for resetting the Control Panel RESET The 10 digit numeric keypad allows entry of the three levels of user passwords It ...

Page 2: ...t the other addresses Setting Supervision Use switch S1 SW5 on the ANN 1 to select or deselect supervision If your ANN 1 has a switch with position 1 indicated on the left hand side ignore the printing on the switch SW1 on S1 is at the extreme right hand side of S1 regardless of any other marking To set for supervision S1 SW5 Closed ON To set for non supervision S1 SW5 Open OFF NOTE When you selec...

Page 3: ...To mount the MKB 4 in an EBX 1 2 backbox 1 Install the XEA 1 2 adapter plates and brackets in the EBX 1 2 backbox according to the XEA 1 2 Installation Instructions P N 315 093608 2 Mount the MKB 4 on the right bracket using the hardware supplied with this module as shown in Figure 4 Install 3 screws in the 3 tapped holes in the right flange Leave a 1 8 inch gap between the head of the screw and t...

Page 4: ...ard in the EBX 1 2 Backbox P N 315 093575 5 EBX 1 2 BACKBOX XEA 1 2 ADAPTER PLATE MKB 4 Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN ...

Reviews: