MK7000
Network

Communication Module

Modem Application

Building Technologies

Fire Safety & Security Products

Summary of Contents for MK7000

Page 1: ...MK7000 Network Communication Module Modem Application Building Technologies Fire Safety Security Products ...

Page 2: ... in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Nous nous réservons tous les droits sur ce document ainsi que sur l objet y figurant La partie recevant ce document reconnaît ces droits et elle s engage à ne pas le rendre accessible à des tiers même partiellem...

Page 3: ...placement for K1D 090 24 4 2 Communication Modules 25 4 2 1 Communication Module E1H 120 to CK100 11 no longer on sale 25 4 2 2 Communication Module E1H 121 to MK7011 no longer on sale 26 4 2 3 Communication Module E1H 130 to MK7011 no longer on sale 27 4 2 4 Communication Module K1H 020 to CK100 11 no longer on sale 28 4 2 5 Communication Module K1H 021 to MK7011 no longer on sale replacement mod...

Page 4: ...RBAN Splitter no longer for sale 43 6 1 2 Block diagramm CERBAN Splitter MK7013 44 6 2 MK7022 Partner System IMS2000 no longer for sale 45 6 2 1 Communication Module K1H 021 to MK7022 System IMS2000 no longer on sale 45 6 2 2 MK7022 to Partner system IMS2000 network CERLOOP 46 6 3 MK7024 Atomic clock DCF77 no longer for sale 47 6 3 1 K1H 060 Communication Module to atomic clock DCF77 MK7024 no lon...

Page 5: ...nections to printers or interfaces be ween Central Processor and System Console 1 2 Transmission Modes Various types of modem are available and selection criteria include the required transmission distance the baud rate and local telephone authority regulations V24 28 Modem RS232 signal level converter Single or dual Modems for 4 wire connections up to 1000m depending on the application may be use...

Page 6: ...verter x x 0 0 0 x x 0 0 0 0 0 x x 0 x x x 0 0 0 0 x x x E8D 010 1 V28 300 Signal level converter x K1D 090 3699320001 1 Bell 103 300 FSK Frequency Shiift Keying x x K1D 120 1 Bell 103 V 22 300 1200 FSK Frequency Shiift Keying DPSK Differential Frequency Shiift Keying x 0 x 0 0 x 0 x 0 x K1D 121 4706010001 V 21 V 22 V 22 V 22 bis 300 600 1200 2400 FSK Frequency Shiift Keying DPSK Differential Phas...

Page 7: ...0 K1D 121 K1D 140 K1D 121 K1D 121 K1D 140 foreign 1 km K1D 010 K1D 011 K1D 012 K1D 080 K1D 081 E8D 010 K1D 011 K1D 012 K1D 080 K1D 081 K1D 080 K1D 081 K1D 010 K1D 011 K1D 012 K1D 080 K1D 081 foreign K1D 090 K1D 121 K1D 140 K1D 121 K1D 140 K1D 121 K1D 121 K1D 140 foreign 10 km K1D 040 K1D 090 K1D 120 K1D 121 K1D 140 E8D 020 K1D 121 K1D 140 K1D 120 K1D 121 K1D 120 K1D 121 foreign K1D 090 K1D 121 K1D...

Page 8: ...1D 012 1 1 1 1 1 1 K1D 080 1 1 1 1 1 1 K1D 081 1 1 1 1 1 1 E8D 010 1 1 1 1 1 0 1 permitted 0 not permitted 2 3 2 FSK PSK QAM Modems currently available modems are printed in bold type Type K1D 020 K1D 040 K1D 090 K1D 120 K1D 121 K1D 140 E8D 020 K1D 020 0 1 1 0 0 0 1 K1D 040 1 0 1 0 0 0 0 K1D 090 1 1 1 0 0 0 1 K1D 120 0 0 0 1 1 PSK 0 FSK 1 PSK 0 FSK 0 K1D 121 0 0 0 1 PSK 0 FSK 1 1 0 K1D 140 0 0 0 1...

Page 9: ...face has been greatly simplified using only 7 of the recommended 22 connections Foreign modems which fulfill the following specification may also be used asynchronous full duplex standard data transmission rate of 300 600 1200 2400 4800 9600 Baud Note conversion to TTL level via CERBERUS Modem necessary Modem Header TTL Level K1D 010 K1D 011 K1D 080 K1D 090 K1D 120 K1D 080 K1D 120 K1D 012 K1D 140 ...

Page 10: ...op bits transmission mode asynchronous bit serial full duplex 2 4 3 Table showing data formats used in DMS7000 Equipment Connection Baud rate Format Level q p 19k2 9600 4800 2400 1200 600 300 Bits Prty Stop CERLOOP Network X D 8 E 1 MOD CERLOOP local interface X D 8 E 1 TTL CERBAN D 7 E 2 MOD CT100 11 Processor A B HDLC NRZI TTL CT100 11 Processor B C D 8 1 MOD CT100 11 Processor C B3Q 071 D 8 1 M...

Page 11: ...ble Transmission Mode bit serial full duplex Transmissioin Rate 300 9600 Baud dependent on max line length and equipment application Characteristics log0 3V 12V log1 3V 12V end interface V24 V28 V24 V28 front interface transmission line CGE CERBERUS Geräte Endschnittstelle end interface CGF CERBERUS Geräte Frontschnittstelle front interface max distance 1 000m CGF CGE ...

Page 12: ...2225 Hz 1070 Hz Space Space 2025 Hz FSK Modems using V 21 K1D021 K1D140 end interface CGE front interface CGF 980 Hz Mark Mark 1650 Hz 1180 Hz Space Space 1850 Hz PSK Modems end interface CGE front interface CGF 1200 Hz Mark Mark 2400 Hz 1200 Hz Space Space 2400 Hz QAM Modems end interface CGE front interface CGF 1200 Hz Mark Mark 2400 Hz 1200 Hz Space Space 2400 Hz Note the application specific b...

Page 13: ...ent If it is no longer able to process the telegrams relay contacts close to over bridge the loop node On detection of an open circuit in the transmission direction of the LOOP telegrams will automatically be transmitted in the opposite direction MK7012 CERBAN Node no longer on sale Application and function of the CERBAN Node is similar to that of the CERLOOP Node The basic difference is that the ...

Page 14: ...2 CERBAN Node K1H 060 3 O O O O O O X O O MK7022 Host Adapter K1H 021 3 X X X X O X O X X 1 X combination possible although not used 2 HW modules in parentheses have been superseded 3 no longer on sale 3 2 CS100 Equipment superseded by DMS7000 equipment function comm module control unit CS100 foreign system module 2 CZ10 CZ12 CM100 0 1 CT100 01 CT100 11 CF100 02 CB100 0 2 CD100 0 2 Host LMS CK100 ...

Page 15: ...CM100 CZ10 CZ12 E1H 130 E2H 081 E2H 081 E1H 130 MM7000 replacement replacement from 06 93 serial from 06 93 parallel parallel Baud rate fixed at 1200 Bd Baud rate may be selected 1200 Bd or 2400 Bd Permissible Combinations and Baud Rates parallel up until 06 93 600b s from 07 06 serial K1H021 K1H022 300b s 300b s CS11 CZ10 CZ12 CS11 CZ10 CZ12 600b s 600b s MK7011 K1H021 K1H021 K1H021 300b s 300b s...

Page 16: ...ule is documented once only even if used in several applications Application specific features and adjustments are indicated on the corresponding pages XXX 000 9999999999 CERBUS 64 pin DIN 41612 connector Type Part No 160 100 handle XX XX overall height depends on module type European Format ...

Page 17: ...tion Note HEADER A1 local serial interface terminal 1 GND receive serial interface to network front Interface CGF end interface CGE K1 2 RX receive 1 K1 1 K1 CGF CGE K1 3 GND transmit 3 2 1 3 2 1 K1 4 TX transmit 3 4 3 4 Pos Programming point to point connection multi point connection CERTER CGE end interface master CGF front interface slave resistor 143 56K6 56K6 link 197 ...

Page 18: ...K1D 011 3 4 2 1 K1 3 4 2 1 K1 end interface CGE front interface CGF A1 A1 point to point connection 3 4 2 1 K1 3 4 2 1 K1 end interface CGE master front interface CGF slave A1 A1 multi point connection 3 4 2 1 K1 front interface CGF slave A1 143 197 143 197 143 197 197 143 197 143 197 resistor link 143 ...

Page 19: ...rogramming below 6 6 connector X10 connection to chassis ground in extreme EM environments lightening HF fields etc not required with Modem Filter M3P 030 green LED H1 1 TX signal transmit data ON power ON flashing data transmission in progress H1 2 flashing data transmission in progress H2 3 4 yellow LED H2 3 RX signal receive data ON corresponding modem line TX connected flashing data reception ...

Page 20: ...er supply 5VDC 5 0 5VDC X11 A1 2 3 4 2 1 K1 5 6 Applications requiring Modem Filter M3P 030 F 1 H 2 E 3 G 4 B 4 D 3 C 1 A 2 M3P 030 F 1 H 2 E 3 G 4 B 4 D 3 C 1 A 2 M3P 030 3 4 2 1 K1 A1 2 5 6 X10 X10 Note X10 MUST NOT be connected to chassis ground when Modem Filter is used chassis ground OP IP IP OP 3 4 2 1 K1 5 6 chassis ground IP Connected with line OP Connected with modem 1 From July 1st 2004 ...

Page 21: ...1 terminal 1 GND receive serial interface to network front interface CGF end interface CGE CERLOOP K1 2 K2 2 TX receive to network K2 1 CGF CGE 1 K2 1 K2 3 3 GND transmit K 3 4 2 1 3 4 2 1 3 4 2 1 4 4 RX transmit 2 1 K1 4 2 1 4 K1 2 1 4 K1 5 0V option external power 3 4 2 5 3 4 2 5 3 4 2 5 6 5V external power supply 5 6 5 6 5 6 Modem 1 Modem 2 Programming CERLOOP CERBAN insert Relay Card K3G 030 p...

Page 22: ...1 K1 A1 5 6 chassis ground chassis ground OP IP IP OP A2 3 4 2 1 K2 3 4 2 1 A2 K2 198 197 144 143 198 197 144 143 3 4 2 1 K1 end interface CGE K1 master front interface CGF K1 K2 slave A1 A1 5 6 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 3 4 2 1 A2 K2 198 197 144 143 198 197 143 A1 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 198 197 144 143 CERLOOP connection A1 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 198 197 144 143 A1 3 4 2 1 K1 5 6 A...

Page 23: ... 6 4 5 6 connector X10 connector X9 option ground connection for aplications in extreme EM environments lightening HF fields etc not required with external Modem Filter M3P 030 green LED H1 1 green LED H3 1 TX signal transmit data ON power ON CERLOOP bypass relay energised flashing data transmission in progress H4 3 4 1 2 H3 2 2 flashing data transmission in progress H2 3 4 1 2 yellow LED H2 3 yel...

Page 24: ...3 4 2 1 A2 K2 X14 X13 X14 X13 3 4 2 1 K1 end interface CGE K1 master front interface CGF K1 K2 slave A1 2 A1 2 5 6 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 3 4 2 1 A2 K2 198 197 X14 X13 A1 2 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 CERLOOP A1 2 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 A1 2 3 4 2 1 K1 5 6 A2 3 4 2 1 K2 Modem 1 Modem 2 Modem n remove links BR1 BR4 on all modems and insert 4 Relays part no 4634980001 chassis ground IP ...

Page 25: ... K1 123 S 1 2 3 4 Pot 110 must not be adjusted chassis ground required for end interface only Pos Function Note HEADER A1 local serial interface terminal 1 transmit and receive serial interface to network connection only permitted via Filter M3B 010 K1 2 receive serial interface to network K1 3 5VDC not used 4 watchdog 4 8s not used Pos Programming DIP FIX CGE end interface CGF front interface 121...

Page 26: ...ADER A2 local serial interface terminal K1 1 terminal K2 1 transmit receive serial interface to network K1 2 K2 2 receive Modem 1 Modem 2 Programming CERLOOP CERBAN K1 answer K2 originate CGE end interface CGF front interface baud rate 1200 Bd PSK 1200 Bd PSK 300 Bd FSK 1200 Bd PSK 300 Bd FSK 1200 Bd PSK DIL switch S1 1 DIL switch S1 3 OFF OFF ON OFF ON OFF S1 2 S1 4 ON OFF OFF OFF ON ON D1 equipm...

Page 27: ...data reception in progress green LED H1 2 green LED H2 4 TX transmit flashing data transmission in progress push button S1 reset press push button after modifying DIL switch S2 Modem 1 Modem 2 Programming CERLOOP insert 2 relays N11 N12 CERBAN insert 2 relays N11 N12 part no 4634980001 CGE end interface CGF front interface baud rate 1200 Bd PSK 2400 Bd AM 300 Bd FSK 600 Bd PSK 300 Bd FSK 600 Bd PS...

Page 28: ... network yellow LED H1 1 RX receive flashing data reception in progress green LED H1 2 TX transmit flashing data transmission in progress push button S1 Reset press button after modifying DIL switch S2 Pos Programming CGE end interface CGF front interface baud rate 300 Bd FSK 600 Bd PSK 300 Bd FSK 600 Bd PSK DIL switch 1 OFF OFF OFF OFF 2 OFF ON OFF ON S2 3 ON originate OFF answer S2 4 OFF 8 data ...

Page 29: ... HEADER A3 A1 A2 ACIA MPU 74 73 EPROM RAM ACIA ACIA E1H 120 4233570001 CERBUS Application CK100 11 CERLOOP Node Note Pos Function A1 network CERLOOP loop node A2 p A3 local interface data transfer Pos Programming Note EPROM file name CK1002 __ EPROM 8k x 8Bit memory RAM 8k x 8Bit factory fitted links 73 factory settings 74 1 configuration using SWE100D2 or CDEDT Flex ...

Page 30: ...11 CERLOOP Node Note Pos Function connector LED s A1 2 CERLOOP network A3 4 A3 local interface A4 not used data transfer H1 1 fault LOOP K1 A1 H1 1 2 2 fault LOOP K2 A2 H1 H2 3 fault local interface A3 4 not used Application MK7011 CERLOOP Node Note Pos Funktion switches Switch S1 Reset Switch S2 ON OFF Default Function S2 1 2400 1200 1200 CERLOOP A1 2 1 2 3 4 S2 2 NO NO NO no function S2 3 600 30...

Page 31: ...ation MK7011 CERLOOP Node Note Pos Function connector LED s A1 2 CERLOOP network H1 1 fault LOOP K1 A1 H1 1 2 2 fault LOOP K2 A2 H1 Application MK7011 CERLOOP Node Note Pos Funktion switches Switch S1 Reset Switch S2 ON OFF Default Function S2 1 2400 1200 1200 CERLOOP A1 2 1 2 3 4 S2 2 NO NO NO no function S2 3 600 300 300 local interface A3 OFF S2 4 Test Normal Normal factory test OFF S3 address ...

Page 32: ...A K1H 020 3698770001 1 2 K1 Application CK100 11 CERLOOP Node Note Pos Function connector terminal A1 network CERLOOP Loop node A2 p A3 local interface data transfer K1 1 24VDC voltage range 10 30VDC 2 GND g g Application CK100 11 CERLOOP Node Pos Function RAM EPROM links Note EPROM file name CK1002 __ EPROM 8k x 8Bit program memory RAM 8k x 8Bit factory fitted links 73 factory settings 74 ...

Page 33: ...connector LED s terminals A1 2 CERLOOP network A3 4 A3 local interface A4 not used data transfer H1 1 fault LOOP K1 A1 H1 1 2 2 fault LOOP K2 A2 H1 H2 H2 3 fault local interface A3 3 4 H2 4 not used 3 4 K1 1 24VDC voltage range 10 30VDC 2 GND g g Application MK7011 CERLOOP Node Note Pos Funktion switches Switch S1 Reset Switch S2 ON OFF Default Function S2 1 2400 1200 1200 CERLOOP A1 2 1 2 3 4 S2 ...

Page 34: ...on MK7011 CERLOOP Node Note Pos Function connector LED s terminals A1 2 CERLOOP network A3 4 A3 local interface A4 not used data transfer H1 1 fault LOOP K1 A1 H1 1 2 2 fault LOOP K2 A2 H1 H2 H2 3 fault local interface A3 3 4 H2 4 not used 3 4 K1 1 24VDC voltage range 10 30VDC 2 GND g g Application MK7011 CERLOOP Node Note Pos Funktion switches Switch S1 Reset Switch S2 ON OFF Default Function ON ...

Page 35: ...ERLOOP Node Note Pos Function connector LED s terminals A1 2 CERLOOP network A3 4 A3 local interface to FS20 Cerloop GW or TELMON via Modem K1D 012 A4 not used data transfer H1 1 fault LOOP K1 A1 H1 1 2 2 fault LOOP K2 A2 H1 H2 H2 3 fault local interface A3 3 4 H2 4 not used 3 4 K1 1 24VDC voltage range 10 30VDC 2 GND g g Application MK7011 CERLOOP Node Note Pos Funktion switches Switch S1 Reset S...

Page 36: ...S7000 A1 fault DMS7000 A1 H1 1 2 2 fault host A2 fault host A2 H1 H2 H2 3 no function no function 3 4 H2 4 no function no function 3 4 K1 1 24VDC 24VDC voltage range 10 30VDC 2 GND GND g g 10 30VDC Application MK7022 communication unit CERLOOP MK7022 communication unit CERBAN Note Pos Funktion switches Funktion switches Switch S1 Reset Reset Switch S2 ON OFF Default Function ON OFF Default Functio...

Page 37: ...D 081 V24 28 A1 A2 MPU ACIA DUSSC F14E 320 A1 2 A2 K1D 081 V24 28 A1 A2 remove links X15 X18 A1 A2 MPU ACIA DUSSC F14A 320 F14A 320 A1 A2 K1D 120 FSK PSK A1 A2 MPU ACIA DUSSC F14E 320 A1 2 K1D 121 FSK PSK QAM A1 A2 new modem A1 A2 K1D 080 V24 28 F14E 320 A1 2 MPU A1 A2 coloured edge A3 4 A1 2 A2 K1D 081 V24 28 F14E 320 A1 2 MPU A1 A2 A3 4 A1 2 A2 K1D 081 V24 28 F14A 320 A1 2 MPU A3 4 A1 A2 K1D 120...

Page 38: ...A2 K1 1 2 K2 1 2 K1D 120 A1 A2 coloured edge coloured edge F14E 320 to K1H 022 A1 2 K1H 022 A1 2 A3 4 1 2 GND 10 30VDC cable F14E 320 must be used with modems K1D 080 K1D 120 CERLOOP CERLOOP CERLOOP CERLOOP or or Not for new installations M3P 030 1 M3P 030 1 max 50cm Control unit CS11 Gateway CK1142 43 local serial interface A1 F14E 320 A2 Modembox B3D021 PC Service Interface E3H 020 E3H 021 ST2 c...

Page 39: ... A1 2 K1 1 2 K2 1 2 K1D 121 A1 A2 F14E 320 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 coloured edge coloured edge F14E 320 to K1H 061 A1 2 K1H 061 A1 2 A3 4 1 2 GND 10 30VDC cable F14E 320 must be used with modems K1D 080 K1D 120 CERLOOP CERLOOP CERLOOP CERLOOP or or Not for new installations M3P 030 1 M3P 030 1 max 50cm K1 A1 2 K1 1 2 3 4 K1D 012 M3P 030 1 F14A320 F...

Page 40: ...A1 2 K1 1 2 K2 1 2 K1D 121 A1 A2 F14E 320 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 coloured edge coloured edge F14E 320 to K1H 021 A1 2 K1H 021 A1 2 A3 4 1 2 GND 10 30VDC control units CZ10 CZ12 CS4 end interface F14A 320 cable F14E 320 must be used with modems K1D 080 K1D 120 CERLOOP CERLOOP CERLOOP CERLOOP or or 1 From July 1st 2004 M3P 030 must be used in new in...

Page 41: ...1 1 2 K2 1 2 K1D 120 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 2 K1 1 2 K2 1 2 K1D 121 A1 2 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 081 A1 F14E 320 A2 A1 F14E 320 to E1H 120 A2 A1 2 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 081 F14A 320 to E1H 120 or remove links X15 X18 from Modem K1D 081 if using ribbon cable F14A coloured edge coloured edge CERLOOP CERLOOP CERLOOP CERLOOP CERLOOP or or A1 A2 A1 A2 1 From July...

Page 42: ...ocal serial interface service interface A1 2 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 081 F14A320 A1 2 K1 1 2 K2 1 2 K1D 121 A1 A2 F14E 320 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 F14E 320 to E1H 121 A1 2 coloured edge coloured edge coloured edge cable F14E 320 must be used with modems K1D 080 K1D 120 or or CERLOOP CERLOOP CERLOOP CERLOOP 1 From July 1st 2004 M3P 030 must...

Page 43: ... Pos 1 6 1 2 3 4 E2H 081 A1 2 A3 4 K1 MPU D1 D2 P1 P2 A1 A2 F14E 320 service interface A1 2 K1 1 2 K2 1 2 K1D 121 coloured edge A1 A2 F14E 320 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 F14E 320 E1H 130 A1 2 coloured edge coloured edge cable F14E 320 must be used with modems K1D 080 K1D 120 or CERLOOP CERLOOP CERLOOP CERLOOP or 1 From July 1st 2004 M3P 030 must be us...

Page 44: ...local serial interface A2 A1 2 K1 1 2 3 4 K1D 012 Partner System K1H 021 A1 2 A3 4 1 2 GND 10 30VDC F14E 320 A1 A2 A1 2 K1 1 2 3 4 K1D 012 A1 2 K1 1 2 3 4 K1D 012 K1D 140 K1D 140 50cm A2 A3 A1 2 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 081 or Partner System F14A 320 Control unit CZ10 CZ12 CZ4 Data concentrators MD7000 Evaluation equipment MC MT7000 coloured edge coloured edge 1 From July 1st 2004 M3P 030 ...

Page 45: ... 2 K1 1 2 3 4 K1D 012 50cm A1 F14E 320 A2 PC Service Interface Control unit CS11 Gateway CK1142 43 A1 A2 PC Service Interface F14E 320 8 9 1011 ST2 X2 E3H 020 E3H 020 E3H 021 ST2 A2 A3 50cm A1 2 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 081 oder Partner System F14A 320 coloured edge coloured edge coloured edge coloured edge 1 From July 1st 2004 M3P 030 must be used in new installations for CE conformity 1 ...

Page 46: ... 1 2 K1D 121 F14A 320 CERLOOP CERLOOP A2 A1 F14E 320 A1 A2 F14E 320 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 oder F14E 320 K1H 022 A1 2 MK7011 CERLOOP node CERLOOP CERLOOP coloured edge coloured edge coloured edge oder cable F14E 320 must be used with modems K1D 080 K1D 120 1 From July 1st 2004 M3P 030 must be used in new installations for CE conformity 2 Replaceme...

Page 47: ...rminals A1 2 A1 end interface CGE01 A2 end interface CGE02 network CERBAN A3 4 A3 front interface CGF01 locale Interface A4 not used data transfer H1 1 fault CGE01 A1 H1 1 2 2 fault CGE02 A2 H1 H2 H2 3 fault CGF01 A3 3 4 H2 4 no function 3 4 K1 1 24VDC voltage range 10 30VDC 2 GND g g Application MK7013 CERBAN Splitter Note Pos Funktion switches Switch S1 Reset Switch S2 ON OFF Default Function S2...

Page 48: ... 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 F14E 320 K1H 021 A1 2 K1H 021 A1 2 A3 4 1 2 GND 10 30VDC Control unit CZ10 CZ12 CS4 F14A 320 CGE01 CGE02 CGE01 CGE02 CERBAN CERBAN CGE01 CGE02 CGE01 CGE02 CERBAN CERBAN or or cable F14E 320 must be used with modems K1D 080 K1D 120 coloured edge coloured edge 1 From July 1st 2004 M3P 030 must be used in new installations for CE conformity ...

Page 49: ...ctor LED s terminals A1 2 A1 local interface A2 ISO 1745 interface network A3 4 A3 not used A4 not used data transfer H1 1 fault A1 DMS7000 H1 1 2 2 fault A2 HOST H1 H2 H2 3 no function 3 4 H2 4 no function 3 4 K1 1 24VDC voltage range 10 30VDC 2 GND g g Application MK7022 Partner System IMS2000 Note Pos Funktion switches Switch S1 Reset Switch S2 ON OFF Default Function 1 2 3 4 S2 1 600 1200 1200...

Page 50: ...1 1 2 K2 1 2 K1D 121 or F14A 320 CERLOOP CERLOOP A2 A1 F14E 320 A1 A2 F14E 320 A1 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 080 A1 A2 K1 1 2 K2 1 2 K1D 120 A1 A2 F14E 320 K1H 021 A1 2 MK7011 CERLOOP Knoten MK7022 Partner System CERLOOP CERLOOP or cable F14E 320 must be used with modems K1D 080 K1D 120 coloured edge coloured edge coloured edge 1 From July 1st 2004 M3P 030 must be used in new installations f...

Page 51: ...ork CERLOOP A3 4 A3 connection atomic clock DCF77 data transfer A4 CERBAN front interface CGF01 netzwok CERBAN H1 1 fault LOOP K1 A1 H1 1 2 2 fault LOOP K2 A2 H1 H2 H2 3 fault atomic clock DCF77 3 4 H2 4 fault CERBAN CGF01 A4 3 4 K1 1 24VDC voltage range 10 30VDC 2 GND g g Application MK7024 atomic clock Bemerkung Pos Funktion Taster Switch g Switch S1 Reset Switch S2 ON OFF Default Funktion S2 1 ...

Page 52: ...nection atomic clock DCF77 A1 2 K1 1 2 3 4 K1D 012 or CERBAN connection atomic clock DCF77 F14E 320 A1 2 A2 5 6 K1 1 2 3 4 K2 1 2 3 4 K1D 081 F14A320 A1 2 K1 1 2 K2 1 2 K1D 121 or K1H 060 A1 2 A3 4 1 2 GND 10 30VDC CERLOOP connection atomic clock DCF77 A1 2 K1 1 2 3 4 K1D 012 F14A320 coloured edge 1 From July 1st 2004 M3P 030 must be used in new installations for CE conformity M3P 030 1 M3P 030 1 ...

Page 53: ...module for Cerloop node only K1H 061 S54469 A1 A1 1 7 Flat cable 0 25m F14A 230 4029670001 8 Flat cable 0 5m F14A 320 3196520001 1 2 1 1 2 1 1 2 9 Flat cablel 0 5m with 3 connectors F14E 320 4514390001 1 1 1 2 1 1 1 1 10 Modem V24 28 K1D 012 4637600001 1 1 1 1 1 1 1 1 Modem Filtermodule M3P 030 3787440001 1 1 1 1 1 1 1 1 2 11 ModemFSK PSK K1D 140 4706140001 1 1 12 Dual Modem V24 28 and relays to K...

Page 54: ...t no Edition e1062i 10 2008 International Headquarters Gubelstrasse 22 Fire Safety Security Products 6301 Zug Switzerland Manual Section MK7000 4 Siemens Switzerland Ltd Building Technologies Division Tel Fax www siemens com buildingtechnologies 41 41 724 24 24 41 41 723 35 22 ...