P212 mA Output Minimum
Sets the minimum mA limit for the output selected, outputs 1 to 3 (P212 - 01 to - 03). The
limit sets the lower mA range (0 or 4 mA) to a minimum output value. (
f
= 3.80)
Enter limit value, range 0 - 22
P213 mA Output Maximum
Sets the maximum mA limit for the output selected, outputs 1 to 3 (P213 - 01 to - 03). The
limit sets the upper mA range (20 mA) to a maximum output value. (
f
= 22.00)
Enter limit value, range 0 - 22.
P214 4 mA Output Trim
Trims the 4 mA output level for the output selected, outputs 1 to 3 (P214 - 01 to – 03). The
trim adjust the output to agree with a milliameter or other external mA input device.
Scroll the trim value up or down
P215 20 mA Output Trim
Trims the 20 mA output level for the output selected, outputs 1 to 3 (P215 - 01 to - 03). The
trim adjust the output to agree with a milliammeter or other external mA input device.
Scroll the trim value up or down
P220 mA Output Damping
Sets the damping for the output selected, outputs 1 to 3 (P220 - 01 to - 03). Damping sets
the speed at which the mA output reacts to change. The greater the damping value, the
slower the response. If the value is 0, the mA output assumes the damping set in P080.
(
f
= 0.00)
Enter the damping value, range 0.001 – 999
P250 mA
input
range
Sets the mA range for the input selected, inputs 1 to 2 (P250 - 01 to - 02).
Entry:
1 = 0 - 20 mA
2 = 4 - 20 mA
f