MD-P1 Point Map by Application Number with Point Map Comparison
Table 4: MD-P1 Point Map by Application Number with Point Map Comparison to DEM1000, DEM2000
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
1
LAI
3
ADDRESS
99
MD-P1 rotary hex switch (MSB and
LSB) on front of meter
1
0
∙
∙
∙
∙
2
LAO
4
APPLICATION
Application
Number
P1 Application Number based on
selected CT Current Range
(can only change via WCIS tool)
1
0
∙
∙
∙
∙
3
LAI
3
FREQUENCY
Hz
0
Measured Line Frequency
0.1
0
∙
∙
4
LAI
3
KW DEM MAX
kW
0
System Maximum Power Demand
or Peak Demand
- returns max demand value read
since startup or reset of demand
register
0.1
0
∙
∙
5
not used
not used
6
LAI
3
KW DEM MIN
kW
0
System Minimum PowerDemand
- returns min demand value read
since startup or reset of demand
register
0.1
0
∙
∙
7
LAI
3
KW
kW
0
System Total True Power =
ABS(kW L1) + ABS(kW L2) +
ABS(kW L3)
0.1
0
∙
∙
8
LAI
3
CONSUMPTN LO
kWh
0
System Total Net True Energy LSW
=ABS(kWh L1) + ABS(kWh L2) +
ABS(kWh L3)
1.0
0
∙
∙
∙
∙
9
LAI
3
CONSUMPTN HI
kWh
0
System Total Net True Energy
MSW
=ABS(kWh L1) + ABS(kWh L2) +
ABS(kWh L3)
1.0
0
∙
∙
∙
∙
10
LAI
3
DEMAND
kW
0
System Average Power Demand
0.1
0
∙
∙
∙
∙