Step 4)
Putting it all together
VIA MODBUS RTU (SERIAL) USING FUNCTION CODE 6 / WRITE SINGLE REGISTER
ID FC ADDR DATA CRC
(note CRC order is swapped)
01 06 08 AA
42 C8
9A BC
01 06 08 AB
00 00
FA 4A
VIA MODBUS RTU (SERIAL) USING FUNCTION CODE 16 / WRITE MULTIPLE REGISTER
ID FC ADDR #REGS LN DATA0 DATA CRC
01 10 08 AA 00 02 04
42 C8 00 00
8B EE
VIA MODBUS TCP (ETHERNET) USING FUNCTION CODE 6 / WRITE SINGLE REGISTER
TXNID PROID LENGT ID FC ADDR DATA
(TXNID will be arbitrary)
01 87 00 00 00 06 01 06 08 AA
42 C8
01 88 00 00 00 06 01 06 08 AB
00 00
VIA MODBUS TCP (ETHERNET) USING FUNCTION CODE 16 / WRITE MULTIPLE REGISTER
TXNID PROID LENGT ID FC ADDR #REGS LN DATA0 DATA1
01 87 00 00 00 0B 01 10 08 AA 00 02 04
42 C8 00 00
Commands Requiring a Processor Reset
Register manipulation of communication protocols or addressing require that the MD-xxHD perform a
“soft reset” in order to take effect. Register 2100 can receive a user command to facilitate this process.
BACnet users write a
1
and Modbus users write
1234
to effect a soft reset. The MD-xxHD reboot time is
approximately 10 seconds.
See the Modbus examples document on the DENT Instruments web site or included with your electronic
documentation for additional support on programming Modbus. The following online resources are also
helpful.
http://Modbus.org/docs/PI_MBUS_300.pdf
http://www.Modbustools.com/Modbus.html
http://www.simplyModbus.ca/TCP.htm
Windows Calculator (Programmer mode)
Summary of Contents for MD-12HD
Page 1: ...ii Siemens Industry Inc User Guide MD 12HD MD 48HD Networked Metering Systems A6V11564207 ...
Page 2: ......
Page 27: ...Siemens Industry inc 26 Configuring Electrical Components using ViewPoint HD ...
Page 68: ...67 Siemens Industry Inc Menu Navigation ...
Page 69: ...Siemens Industry inc 68 Communication Navigation ...