Current Transformer Basics
Ensure CTs meet the following criteria:
▪
600 Vac UL Rated
▪
UL2808 Listed
▪
1/3 (333 mV) output voltage
▪
Appropriate range for the circuit (5-120% of CT rating recommended)
▪
Read the label.
Ensure CT orientation and placement:
▪
Arrow points toward load (or as instructed by CT label).
▪
Arrow points away from Panel (or as instructed by CT label).
▪
Placed on First Conductor of voltage Reference (L1-L2) circuits are
placed on L1.
▪
Observe wiring color and polarity.
▪
Use the Shield wire if provided (connect to PCB terminal marked
S
).
Wiring Guide for CT Types
Split, Hinged, and Solid
Core CTs
RōCoil CTs
White: Positive
Black: Negative
(no shield)
White: Positive
Brown: Negative
Bare Wire: Shield