Siemens Industry, inc.
38
Wiring the MD-xxHD Meter in a 4-wire, 3
ɸ Service Panel
Illustrating the Intended Wiring Configuration for Each of the Service Types
Available in the Service Drop-down List U
nder “Meter Setup”
NOTE:
The MD-xxHD
Meter Series uses the
Neutral
Terminal as a voltage reference. For
systems without a neutral conductor, Siemens suggests connecting a ground wire to
this terminal. If the neutral terminal is left open, L-L measurements will be accurate, but
L-N measurements may not be symmetric. If a ground wire is connected to the Neutral
terminal, <2 mA will flow into the ground wire.
Connect the
Neutral wire
or Ground wire to
V INPUT 1 (N) on
the MD-xxHD
meter
Meter Power
Connect all phases
to the V INPUT 1
terminal
(Label as Disconnect)
3-Wire, 3
ɸ
DELTA load
(No possibility of
Neutral Current)
L1-N, L2-N(est), L3-N
3 Wire, 3
ɸ used
On MAINS
L1-N, L2-N, L3-N
(
R
ōCoils
Shown)
Single Phase
Branch Loads
L1-N
4 Wire, 3
ɸ
WYE load
(Neutral Current)
L1-N, L2-N, L3-N