LOGO! AM2 RTD
Cable length (shielded)
max. 10 m
Interference frequency
suppression
55 Hz
A.13
Technical data: LOGO! AM2 AQ
LOGO! AM2 AQ
Power supply
Input voltage
24 V DC
Permissible range
20.4 ... 28.8 V DC
Power consumption
35 ...90 mA
Voltage failure buffering
typ. 5 ms
Power loss at 24 V
0.9 ... 2.2 W
Electrical isolation
No
Reverse polarity protection
Yes
Ground terminal
for connecting ground and shielding of the analog
output line.
Analog outputs
Number
2
Voltage range
0 ... 10 V DC
Voltage load
≥5 kΩ
Current output
0/4...20mA
Curreny load
≤250 Ω
Resolution
10 bit, normalized to 0 ... 1000
Cycle time for analog output
depending on installation (50 ms)
Electrical isolation
No
Line length (shielded and twisted)
max. 10 m
Error limit
Voltage output: ± 2.5 % FS
Short circuit protection
Voltage output: Yes (affect neighboring voltage output)
Overload protection
Voltage output: Yes (affect neighboring voltage output)
Note
The 0/4 ... 20 mA current output is only possible when the module is used with a LOGO!
0BA6 or LOGO! 0BA7 Base Module.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...