LOGO! functions
4.4 Special functions list - SF
LOGO!
256
Manual, 04/2011, A5E03556174-01
4.4.30
PI controller
Short description
Proportional-action and integral-action controllers. You can use both types of controller
individually or combined.
Symbol in LOGO!
Wiring
Description
Input A/M
Set the mode of the controller:
1: automatic mode
0: manual mode
Input R
Use the input R to reset the output AQ. As long as
this input is set, the input A/M is disabled.
Output AQ is set to 0.
Input PV
Analog value: process variable, influences the output
$ᇄ
$4
$0
5
39
3DU
Parameter
SP: Set-value assignment
Range of values:
-10,000 to +20,000
KC: Gain
Range of values:
00.00 to 99.99
TI: Integral time
Range of values:
00:01 to 99:59 m
Dir: Action direction of the controller
Range of values:
+ or -
Mq: Value from AQ with manual mode
Range of values:
0 to 1000
Min: Minimum value for PV
Range of values:
-10,000 to +20,000
Max: Maximum value for PV
Range of values:
-10,000 to +20,000
A: Gain
Range of values:
±10.00
B: Offset
Range of values:
±10,000
p: Number of decimals
Range of values:
0, 1, 2, 3
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...