![Siemens LOGO! Manual Download Page 121](http://html.mh-extra.com/html/siemens/logo/logo_manual_377208121.webp)
Programming LOGO!
3.8 Configuring additional functions for LOGO! (0BA7 only)
LOGO!
Manual, 04/2011, A5E03556174-01
121
3.8.3
Configuring the Data Log
You can configure the Data Log block only from LOGO!Soft Comfort.
You can configure a maximum of one Data Log for your circuit program using LOGO!Soft
Comfort. The Data Log is used to record process measurement variables of the selected
function blocks. For a detailed description of configuration of the Data Log function in
LOGO!Soft Comfort, refer to the online help for LOGO!Soft Comfort V7.0.
If your circuit program in LOGO! contains the Data Log block, you can configure elements
connected to the block. For more information of configuration of Data Log elements from
LOGO! 0BA7, refer to the topic Data Log (0BA7 only) (Page 285).
3.8.4
Viewing network inputs/outputs
LOGO!Soft Comfort provides you with the following connectors representing network
input/output blocks:
●
Network digital inputs (identified with an NI in LOGO!)
●
Network analog inputs (identified with an NAI in LOGO!)
●
Network digital outputs (identified with an NQ in LOGO!)
●
Network analog outputs (identified with an NAQ in LOGO!)
Network digital or analog inputs can connect with the inputs of function blocks. Network
digital or analog outputs can connect with the outputs of function blocks.
If your circuit program contains a network digital/analog input, LOGO! can read a
digital/analog value from another circuit program in a networked device. If your circuit
program contains a network digital/analog output, LOGO! can write its digital/analog output
value to another networked 0BA7 device in slave mode.
Note
You can only configure these network connectors for your circuit program from LOGO!Soft
Comfort. If your circuit program in LOGO! contains a network connector, you can not make
any edits to the circuit program from the LOGO! onboard display.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...