background image

52,4

90

1

1

1

71,5

P1

P2

P3

2

P1

AC/DC
230V

P2 P3 P4

L1 N

X1:P4

X1:P1

X1:P2

X1:P3

X10

1

1

3

6GK7177-1FA10-0AA0

s

LOGO! CSM230

DC 115...210V                0.02...0.01A

AC 100...240V    ~          0.02...0.01A

X1:P1  TO  X1:P4  FOR  LAN  ONLY

Mounting slides

Hole pattern for wall mounting

Prior to wall-mounting, the mounting slides on the back

of the device are pushed open.

98 +/- 0.3

1

2

P1

AC/DC
230V

P2 P3 P4

X1:P4

X1:P1

X1:P2

X1:P3

L- N

36.0

cULus

C-Tick

- UL 508 Listed

- CSA C22.2 Number 142

AS/NZS 2064 Class A

cULus Haz.Loc.

FM

You can use the device in the following hazardous locations:

IND. CONT. EQ., E223122, UL 1604, UL 2279-15

FM3600 and 3611:

CL. I, Div. 2, Group A, B, C, D, T4

CL. I, Zone 2, Group IIC, T4, Ta = 55°C

Installation, Connection, Technical specifications

2

3

1

EU Directive 2004/108/EC "Electromagnetic Compatibility" (EMC Directive)

-

 Emission: EN 55022 Class B: 2010

-

 Immunity: EN 61000-6-2: 2005

EU Directive 2006/95/EC "Low Voltage Directive" (LVD)

- Safety: EN 61131-2: 2008

The EC Declaration of Conformity is available for all responsible authorities at:

Siemens Aktiengesellschaft

Industry Automation, I IA SC CI

Postfach 4848

D-90026 Nuernberg

Germany

You will find the EC Declaration of Conformity for this product on the Internet 

at the following address:

http://support.automation.siemens.com/WW/view/en/10805878

   → Tab "Entry List"

   Filter settings: Entry type: "Certificates"

   Certificate Type: "Declaration of Conformity"

   Search items(s): <name of the module>

The product meets the requirements and aims of the following EC directives:

Sources of information and other documentation

The "SIMATIC NET Industrial Ethernet Network Manual" contains 

detailed information on the network structure, maximum cable lengths, 

cabling technology etc.

   http://support.automation.siemens.com/WW/view/en/

27069465

   Entry ID:  27069465

You will find additional information on the Siemens LOGO! Web page:

   http://www.siemens.com/logo

Neutral Conductor

N

Conductor

L1

Functional grounding

RJ-45 jacks for connections via Ethernet (10/100 Mbps)

LED for the power supply (AC/DC 230V) and

LEDs for the Ethernet communication status (P1 - P4)

Three screw terminals:

AC  47... 63 Hz

Permitted line power frequency

Technical specifications

All ports adhere to 1.5 kV insulation voltage:

- to shield

- between the ports.

Insulation of the ports

Ethernet interface

300 seconds

Aging Time

1024

Functional grounding can be established by connecting a cable

from terminal 3, for example to the DIN rail. Such a cable should be 

kept as short as possible. Grounding is, however, not necessary for 

interference-free operation.

Functional grounding

Per terminal for L1 and N

Cable cross section: 1 x 2.5 mm2 or 2 x 1.5 mm2

Connection

1.8 W

Effective power loss

- AC 100 ... 240 V:   0.05 ... 0.03 A

- DC 115 ... 210 V:   0.02 ... 0.012 A

Current consumption (I)

AC   100 ... 240 V

DC 115 ... 210 V

Input voltage

Electrical specification

Delay resulting from latency

64 byte

Smallest data packet

1518 byte

Largest data packet

A standard Ethernet cable can be connected to the Ethernet interface.

However, to minimize electromagnetic interference, Siemens 

recommends a shielded Ethernet cable with a twisted pair

(category 5) with a shielded RJ-45 connector at both ends.

Network cable

4 x RJ‑45 jacks with MDI‑X assignment 10/100 Mbps

(half / full duplex), autopolarity, autonegotiation

Communications connector

Star and bus topology

Note that the direct connection of two ports on the switch or

accidental connection over several switches causes an illegal loop.

Such a loop can lead to network overload and network failures.

Topology

When a frame passes through the CSM 230, it is delayed

by the store and forward function of the switch:

- with a 64 byte frame length by approx. 8 μs (at 100 Mbps).

- with a 1518 byte frame length by approx. 125 μs (at 100 Mbps).

Technical specifications

You will find the currently valid approvals on the type plate.

Approvals

http://www.siemens.com/logo

When installing and connecting up, keep to the procedures described in the LOGO! manual.

You will find additional information on the Siemens LOGO! web page:

Entry ID:  50074616

http://support.automation.siemens.com/WW/view/en/50074616

Entry ID:   27069465

http://support.automation.siemens.com/WW/view/en/27069465

Sources of information and other documentation

Prior to installation, connecting up and commissioning, read the relevant sections

in the LOGO! manual:

Installation

Order number: 6GK7177-1FA10-0AA0

Status of LEDs

Product information

© Siemens AG 2012

A5E03733191-04

CSM 230

LOGO!

Meaning

Status

LED

P1 - P4

 

P1 - P4

 

LOGO! receives / sends data via Ethernet.

Power is connected.

The connection via Ethernet is established (link up).

No connection via Ethernet (link down).

Power is not connected or the connected

power is too low.

Off

Off

Flashing

On

On

AC/DC 

230V
AC/DC

230V
P1 - P4

 

IP 20

Degree of protection

35 mm DIN rail (DIN EN 60715 TH35) or wall mounting

Installation

Net weight

155 g

72 (4 TE) x 90 x 55 mm

Dimensions (W x H x D) in mm

< 90% (no condensation)

Relative humidity during operation

- 40°C … +70°C

Transport/storage temperature

0 … 55°C

Operating temperature

Further technical specifications

Learnable MAC addresses

DIN rail mount

2. Press down the lower part until the device locks in place.

    The mounting slide on the back must snap into place.

1. Fit the LOGO! onto the DIN rail.

Pin 8  -   n. c.

Pin 7   -  n. c.

Pin 6   -  TD -

Pin 5   -  n. c. 

Pin 4   -  n. c. 

Pin 3   -  TD +

Pin 2   -  RD -

Pin 1   -  RD +

RJ-45 jacks with MDI-X assignment

Wall mounting

All dimensions in mm

Tightening torque 0.8 ... 1.2 Nm

Hole for screw Ø 4 mm

The "SIMATIC NET Industrial Ethernet Networking Manual" contains detailed information

on the network structure, maximum cable lengths, cabling technology etc.

To fulfill the requirements according radiated emission EN 55022 Class B, the shield of all 

connected LAN cables must be grounded.

Release 06/2012

Reviews: