English
LOGO! PROM
Operating Instructions, 02/2010, A5E02562962A-02
7
When all the modules have been removed, you can reset the LEDs by pressing the
"Start/Reset" button.
If new or already programmed modules are inserted, you can reset all the LEDs by pressing
the "Start/Reset" button and the programming procedure is then started again.
How to duplicate via a PC cable
LOGO! Soft Comfort V5.0/V6.0 is the prerequisite for downloading via a PC cable.
The PC cable is plugged in instead of the master cable and must also remain plugged in
after the download. A programming procedure cannot be started when the cable is not
plugged in.
The download is started from LOGO! Soft Comfort, the same as with a LOGO! device. The
only difference to programming a LOGO! device is that the LOGO! device type for which the
modules are to be created has to be selected before the download takes place. The user is
responsible for the correct selection of the device types.
After transfer has been initiated an inquiry is made for the 0BA4/0BA5/0BA6 device line as to
whether copy protection is desired.
After the download the programming procedure can be carried out in the same way as for
"duplicating with master module", but with the PC cable plugged in.
NOTICE
LOGO! devices with the designation 6ED1xxx-xxxx-0BA0 can be selected in
LOGO! Soft Comfort, but the data transfer is not executed and the master LED flashes red.
Technical specifications
Input voltage
7 to 15 V AC/DC
Current consumption
< 50 mA
Reverse polarity protection
Available
Overvoltage protection
Not available
Ambient temperature during operation
+ 5 ... + 45 °C
Storage temperature
- 20 ... + 70 °C
Humidity
Condensation not permissible
Power supply unit,
included in scope of supply
100 to 230 V AC
50 / 60 Hz
CAUTION
The device is only allowed to be used in closed rooms.
Siemens Parts