Configuration (WBM)
5.13 Monitoring
LOGO! CMR2020, LOGO! CMR2040
110
Operating Instructions, 10/2016, C79000-G8976-C356-03
●
"Constants tab"
For writing access to the BM by SMS, here you specify fixed values for the variables to be
written.
●
"Message texts tab"
You create texts you want to send using SMS or e-mail. You assign symbolic names to
the message texts.
You configure the sending of these texts to a recipient or recipient group as an action in
the "Actions" tab. You assign this action to an event in the "Assignments" tab.
●
"Signals tab"
You first specify which signals from the BM or the CMR you want to monitor; e.g. the
digital input 1 (I1) of the BM.
You can give all signals symbolic names.
●
"Events tab"
For the selected signal, you configure an event, for example I1 “Changes to 0".
●
"Actions tab"
You specify one or more actions, initially not associated with an event:
–
Send an SMS message or e-mail to a recipient group
–
Set an output in the CMR
–
Send an SMS message with the process image
–
Forward a GPS position to LOGO! BM
–
Change the program status of the LOGO! BM .
You can give all actions symbolic names.
●
"Assignments tab"
You assign certain actions to the configured events, for example sending an SMS
message to a particular recipient group if an output of the BM changes.
In the lower part of the page under “If:" and "Then:" you will see which action will be
executed along with all the set parameters.
5.13.3
Overview
All configured signals of the BM and the CMR are displayed with symbolic names and their
current status.
After resetting to factory settings, the inputs and outputs of the CMR are displayed as when
shipped.
Display if the connection between the CMR and BM is interrupted
●
In the "LOGO! BM" tab, you have configured a connection between the CMR and BM.
●
You have configured LOGO!-BM signal types in the “Signals" tab .