
Technical
Instructions
LMV
Series
Document
No.
LV5
‐
1000
Section
7
Page
20
SCC
Inc.
Unsuccessful
VSD
Standardization
For
information
on
what
VSD
standardizing
is
or
how
to
perform
standardization,
see
Section
5.
The
standardized
speed
can
be
viewed
using
the
following
menu
path:
Params
&
Display
>
VSD
Module
>
Configuration
>
Speed
>
StandardizedSp
For
a
3600
RPM
motor,
the
standardized
speed
is
typically
3500
+/
‐
100
RPM.
If
this
is
the
case,
the
standardization
was
successful.
If
the
VSD
does
not
standardize
successfully,
check
the
following:
1.
The
VSD
cannot
standardize
if
the
safety
loop
is
open.
Check
that
the
safety
loop
is
closed
by
making
sure
there
is
120
VAC
on
terminal
X3
‐
03.1.
If
there
is
not,
check
the
limits
in
the
safety
loop
and
the
burner
flange
to
see
which
limit
is
open.
2.
Ensure
that
the
LMV52
is
not
in
alarm.
If
so,
reset
the
fault
and
attempt
to
standardize
again.
3.
Verify
the
speed
wheel
is
installed
on
the
blower
motor
correctly
and
the
gap
between
the
speed
sensor
and
the
speed
wheel
is
correct
(about
1/16”).
Also,
use
Section
2
to
verify
that
the
wiring
from
the
speed
sensor
to
the
LMV52
is
correct.
The
yellow
LED
on
the
back
of
the
speed
sensor
should
blink
every
time
a
speed
wheel
“finger”
passes
by
the
nose
of
the
sensor.
If
it
does
not
blink,
the
sensor
is
wired
incorrectly,
the
sensor
is
mounted
too
far
from
the
speed
wheel,
or
the
sensor
is
defective.
4.
Check
to
ensure
that
the
air
damper
opens
when
the
standardization
is
activated.
If
this
does
not
happen,
set
the
air
actuator
to
“air
influenced”
using
the
following
menu
path:
Params
&
Display
>
RatioControl
>
Gas/Oil
Settings
>
AirActuator
5.
Check
the
ramp
times
on
the
LMV52
and
the
VSD.
The
ramp
times
on
the
VSD
must
be
faster
(shorter)
than
the
ramp
times
on
the
LMV52.
The
LMV52
ramp
times
can
be
found
using
the
following
menu
paths:
Params
&
Display
>
RatioControl
>
Times
>
OperatRampMod
Params
&
Display
>
RatioControl
>
Times
>
TimeNoFlame
In
general,
the
VSD
ramp
times
should
be
set
about
5
seconds
faster
(shorter)
than
the
LMV52
ramp
times.
HOME
Summary of Contents for LMV 5 Series
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 7 Section 2 HOME ...
Page 42: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 8 SCC Inc HOME ...
Page 43: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 9 Section 2 HOME ...
Page 44: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 10 SCC Inc HOME ...
Page 45: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 11 Section 2 HOME ...
Page 46: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 12 SCC Inc HOME ...
Page 47: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 13 Section 2 HOME ...
Page 48: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 14 SCC Inc HOME ...
Page 49: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 15 Section 2 HOME ...
Page 50: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 16 SCC Inc HOME ...
Page 51: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 17 Section 2 HOME ...
Page 52: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 18 SCC Inc HOME ...
Page 53: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 19 Section 2 HOME ...
Page 54: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 20 SCC Inc HOME ...
Page 55: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 2 HOME ...
Page 373: ...Intentionally Left Blank ...