background image

 

P.T.O. 

instabus

®

Technical Manual

 

Decentralized Power Supply 
JB 125C23, 80mA 

 

5WG1125-4CB23 

April 2020 / Page 1 

USA

 

 

 

Product and Application Description 

 

The decentralized power supply unit JB 125/23 provides the 

system power necessary for the 

instabus

 KNX. The device is 

installed in a 4 x 4 inch junction box. The bus is connected 
via a bus terminal block.

 

The  integrated  choke  prevents  the  data  telegrams  from 
short-circuiting on the bus line.  
For  each  bus  line, at  least one  decentralized  power  supply 
unit JB 125/23 is needed. A second unit is not required un-
less the supply voltage at a bus device is less than 21 V. Up 
to eight decentralized power supply units JB 125/23 may be 
attached in parallel to a single bus line.  

Note: If two or more power supply units are operated in par-
allel on one bus line and if the overload LED is lit on one or 

several power supplies, then the bus configuration has to be 

changed until the overload display disappears on all units.  

A minimum cable length is not required between the decen-
tralized  power  supplies  JB 125/23.  Operation  of  a  power 
supply  unit  N125/x2  in  parallel  to  the  decentralized  power 
supplies  is  permitted  on  the  same  bus  line  as  long  as  the 
sum  of  all  short  circuit  currents  of  all  power  supplies  does 
not exceed 3A.    
When  several  bus  devices  are  installed  in  short  bus  cable 
distance (e.g. 10 m), e.g. in distribution boards, or in a room 
control  box  AP 641,  the  power  supply  units  shall  be  ar-
ranged near these bus devices. The distance along the bus 
wire between any bus device and the closest power supply 
unit must not exceed 350 m. 

If only the decentralized power 

supply  JB 125/23  is  used,  then  the  maximum  KNX  cable 
length  in  a  bus  line  is  350m  for  one,  700m  for  two,  and 
1000m  for  3  or  more  decentralized  power  supplies 
JB 125/23.

 

The  decentralized  power  supply  unit  JB 125/23  has  a  volt-
age  and  current  regulation  and  is  therefore  short-circuit 
proof. Short power failures can be bridged with a backup in-
terval of at least 100 ms. 

To ensure an uninterrupted power supply a separate circuit 
with  safety  separation should  be  used  for  the  mains  power 
supply circuit of all power supply units. 
 
The  decentralized  power  supply  units  JB 125C23  are  pow-
ered by AC 120V.  
 
 
 
 

Application Program 

 

No application program required 
 
 
 
 
 
 
 

Technical Specifications 

 

Input voltage 

• rated voltage: AC 120V, 50...60Hz 
 

Rated power consumption 

approx. 10 W 
 

Output voltage 

• rated voltage: DC 29 V (class 2) 
• safety extra low voltage (SELV) 
• permissible range: DC 28 ... 30 V 
 

Output current 

• rated current 80 mA 
• short-circuit current: limited to 0.2 A  
 

Backup interval 

on input voltage failure: 

≥ 100 ms at rated current 

 
 

Display elements 

• 1 red LED: for indicating  

- a shorted-out bus line or device over-load 

 

 

 

Connections 

 

Bus line : Bus connection pins for connection of the 
screwless bus terminal block (red-

black) 0.6…0.8

 mm Ø 

single core, strip insulation 5mm 

 

mains power:  
see Location and Function of Interface Elements 
 

Physical specifications 

 

housing: plastic 

 

dimensions (L x W x D):  
length : 70 mm (2.76 inch) 
width: 90 mm (3.54 inch) 
depth: 44.6 mm (1.76 inch) 

 

weight: approx. 171 g 

 

fire load: approx. 5 MJ 

 

Installation: in a junction box (min. dimensions (L-W-D)) 
Length: 4 inch (101.6 mm) 
Width: 4 inch (101.6 mm) 
Depth: 2 inch (50.8 mm) 

 

Electrical

 

safety

 

 

Degree of pollution (according to IEC 60664-1): 2 

 

Type of protection (according to EN 60529): IP 20 

 

Overvoltage category (according to IEC 60664-1): III

 

 

Bus: safety extra low voltage SELV DC 24 V 

 

Device complies with: EN 50428 

 

Electromagnetic compatibility 

complies with EN 50428 
 

Environmental specifications 

 

Ambient operating temperature:  

5 … + 45 °C  (+ 23 ... + 113 

F) 

 

Storage temperature: 

25 … + 70 °C 

 (- 13 ... + 158 

F) 

 

Relative humidity (not condensing): 5 % 

  93 % 

 

Reliability

 

 

Failure rate: 109 fit at 40°C 

 

Markings 

EIB, KNX, UL 

 

 

Listings and Certifications 

 

CE mark 

complies with the EMC regulations (residential and func-
tional buildings) and low voltage regulations

  

 
UL listed (E464611) 

UL 916, Open Energy Management Equipment 

 
 

 

Reviews: