Advanced device functions
5.1 Monitoring functions
SIMATIC IPC277D
58
Operating Instructions, 12/2016, A5E03409486-AE
5.1.2
Temperature monitoring/display
Temperature monitoring
Three temperature sensors monitor the temperature of the device at several positions:
●
Processor temperature
●
Temperature close to the RAM ICs/chips
●
Temperature of the basic module
A temperature error is triggered when one of the three temperature values exceeds the set
temperature threshold and the following reaction is initiated:
Reaction
Option
The DiagBase or DiagMonitor software is enabled
None
The temperature error is retained in memory until temperatures have fallen below the
thresholds and it is reset by one of the following measures:
●
Acknowledgment of the error message by the monitoring software
●
Restart of the device
5.1.3
Watchdog (WD)
Function
The watchdog is able to monitor program runtime and informs the user about the different
reactions that are triggered if the user program does not respond to the watchdog within the
specified monitoring time.
The watchdog is in idle state during power on of the device or after a HW-RESET (cold
restart). A WD reaction is not triggered while it is in idle state. However, an active watchdog
alarm remains after the restart.
Watchdog reactions
The following reactions may be triggered if the watchdog is not retriggered within the set
time:
Reaction
Option
Trigger a PC reset
Configurable
Output DiagBase alarm messages
None
Note
Contact Customer Support for a detailed description of the Watchdog functions.
Summary of Contents for INOX PRO SIMATIC IPC277D
Page 6: ...Preface SIMATIC IPC277D 6 Operating Instructions 12 2016 A5E03409486 AE ...
Page 22: ...Overview 1 3 Accessories SIMATIC IPC277D 22 Operating Instructions 12 2016 A5E03409486 AE ...
Page 170: ...List of abbreviations SIMATIC IPC277D 170 Operating Instructions 12 2016 A5E03409486 AE ...
Page 182: ...Index SIMATIC IPC277D 182 Operating Instructions 12 2016 A5E03409486 AE WinMove 76 ...