Technical Specifications
10.4 Technical specifications of the IM 153-4 PN interface module
ET 200M
234
Operating Instructions, 12/2008, EWA-4NEB780600602-08
10.4
Technical specifications of the IM 153-4 PN interface module
Order Number
6ES7153-4AA01-0XB0
Properties
The IM 153-4 PN interface module has the following properties:
●
It interconnects the ET 200M with PROFINET IO.
●
A maximum of 12 modules can be operated with the IM 153-4 PN
●
It prepares the data for the inserted modules.
The following settings can be made: SM, CP, non-assignable FM
●
It supplies the backplane bus
●
Integrated switch with 2 ports
●
Transfer and backup of the device name on SIMATIC Micro Memory Card
●
Firmware update using a SIMATIC Micro Memory Card or PROFINET IO
●
The reference potential M of the rated supply voltage of the IM 153-4 PN to the rail
(protective conductor) is connected by means of an RC combination, thus permitting an
ungrounded configuration
●
Supported Ethernet services
–
ping
–
arp
–
Network diagnostics (SNMP): LLDP-MIB / MIB-2
–
Resetting SNMP parameters to the factory settings
–
I&M data
●
Interrupts
–
Diagnostic interrupts
–
Hardware interrupts
–
Removal / insertion interrupts
–
Maintenance interrupts
●
Port diagnostics
●
Port disabling
●
Support for real-time communication (RT Class 1 and Class 2).
●
Maximum address space of 200 bytes I/O data.
●
Data records for I/O modules
●
As of 6ES7153-4AA01-0XB0:
–
Isochronous real-time communication
–
Minimum updating time 250 μs with IRT
–
Prioritized startup
–
Device replacement without removable media / programming device
–
Changing IO devices during operation (changing partner ports)