background image

Models ILP-1/ILPT-1

P/N 315-092594-8

Figure 1

Installation and Wiring Diagram

Fire Safety

Installation Instructions

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

These instructions are written in accordance with the

installation guidelines of NFPA 72, National Fire Alarm

Code,  and  CAN/ULC-S524, The  Installation  of  Fire

Alarm Systems.

CAUTION:  Detector Device Storage

DO  NOT  install  this  detection  device  until  all

construction is completed.
DO NOT store this detection device where it can

be contaminated by dirt, dust, or humidity.

DETECTOR PLACEMENT

Although no specific spacings are set for the detectors

used for a clean air application, use 30 foot center

spacing (900 sq ft) from NFPA Standard 72 Chapter 5

and CAN/ULC-S524, if practical, as a guide or starting

point for a detector installation layout. This spacing,

however, is based on ideal conditions - smooth ceiling,

no  air  movement,  and  no  physical  obstructions.  In

some applications, therefore, considerably less area

is protected adequately by each smoke detector. This

is why it is mandatory to closely follow the installation

drawings. In all installations place the detector on the

ceiling, a minimum of 6 inches from a side wall, or on

a wall, 6 inches from the ceiling.
If  you  have  any  questions  regarding  detector

placement, follow the drawings provided or approved

by  Siemens  Building  Technologies,  Inc.  or  by  its

authorized distributors. This is extremely important!

The detector placements shown on these drawings

were chosen after a careful evaluation of the area that

is protected. Factors such as air currents, temperature,

humidity, pressure, and the nature of the load were

carefully considered. Especially noted were the room

or area configuration and the type of ceiling (sloped

or  flat,  smooth  or  beamed).  Siemens  Building

Technologies, Inc.'s extensive experience in the design

of the system assures the best detector placement by

following  these  drawings.  Sound  engineering

judgement by qualified personnel must be followed.

To avoid nuisance alarms:

Do not locate the detector next to an oil burner, electric

heaters, kitchens, or garages where exhaust fumes

can trigger an alarm. Other causes of false alarms

are dust accumulation, heavy concentrations of steam,

heavy pipe or cigar smoking, 

high relative humidity

or  other  humid  areas  where  condensation  may

occur,

 and concentrated aerosol sprays.

AIR CURRENTS

Before a detector can sense a fire, the products of

combustion or smoke must travel from the fire to the

detector. This  travel  is  especially  influenced  by  air

currents;  therefore,  consider  air  movement  when

designing the system. While combustion products tend

to rise, drafts from hallways, air diffusers, fans, etc.,

may help or hinder the travel of combustion products

Summary of Contents for ILP-1

Page 1: ...es from the ceiling If you have any questions regarding detector placement follow the drawings provided or approved by Siemens Building Technologies Inc or by its authorized distributors This is extremely important The detector placements shown on these drawings were chosen after a careful evaluation of the area that is protected Factors such as air currents temperature humidity pressure and the n...

Page 2: ... 38 C Use the detector in environments where the humidity does not exceed 93 non condensating Normal changes of atmospheric pressure do not affect detector sensitivity The air velocity range is 0 4000 ft min for open areas applications ILP 1 Air Duct Applications In Air Duct applications the Model ILP 1 requires Air Duct Cover P N 305 093076 Do not use the Model ILP 1 with any other air duct cover...

Page 3: ...nly qualified service personnel should test Refer to the MXL MXLV OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 092036 or the MXL IQ OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 093624 as applicable Test as frequently as required by the Installation and Test Guidelines of NFPA 72 Obtain detector sensitivity measurements from the MXL Control Panel Refer to the MXL MXLV MXL IQ Manua...

Page 4: ...es to disengage the locking tabs and then pulling the lower section out 5 Use a small soft brush to loosen dust in the crevices Vacuum any dust from the lower photochamber Do not use cleaners or solvents on the lower photochamber Another method for cleaning the photochamber after removing the lower section is to blow out the dust However do not use compressed air that might contain oils When not u...

Reviews: