Planning
4
Smoke detector
31
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
4.3 Smoke detector
The optical smoke detector OP110 demonstrates quick response behavior in the
event of slow-burning fires that generate smoke. It is extremely well suited to
general-purpose applications.
The smoke detector OP110 has two selectable parameter sets.
4.3.1 Parameter sets
Standard:
For standard applications, such as in corridors, bedrooms, offices, and living
rooms.
The parameter set 'Standard' is automatically set if the point detector is installed
in a detector base DB110 or DB110D.
Sensitive:
For areas with few misleading sources of false alarms, such as cigarette smoke,
exhaust fumes, and steam.
The parameter set 'Sensitive' is automatically set if the point detector is installed
in a detector base DB110R or DB110RD.
4.3.2 Specifications
The table below shows the properties of the parameter set for the smoke detector
OP110:
Name
Response time [s]
Sensitivity [%/m]
Standard
10
2,3
Sensitive
10
1,8
All parameter sets meet the criteria of standard EN 54-7.