Safety notes
2.4 Installation in hazardous area
FUG1010 IP65 NEMA 4X
Operating Instructions, 01/2013, A5E02951519-AC
15
Hazardous area safety requirements
It is required that:
●
Electrical connections are in accordance with EN60079-14 (Installing Electrical Systems
in Explosion Hazardous Areas).
●
The protective cover over the power supply is properly installed. For intrinsically safe
circuits the connection area can be opened.
●
Appropriate cable connectors are used for the output circuits:
–
Intrinsically safe: blue
–
Non-intrinsically safe: black
●
Sensor and transmitter are connected to the potential equalization.
For intrinsically safe output circuits potential equalization must be maintained along the
entire connection path.
●
When protective earth (PE) is connected, no potential difference between the protective
earth (PE) and the potential equalization (PA) can exist, even during a fault condition.
WARNING
Explosion Hazard
"Flameproof enclosure" type of protection
Only open devices with type of protection "Flameproof enclosure" (e.g. FUT1010 NEMA
7) in hazardous areas when the power to the device is turned off, otherwise there is a
risk of explosion.
WARNING
Explosion Hazard
Laying Cables
Cable for use in zone 1 and 2 must satisfy the requirements for having a proof voltage <
AC 500 V applied between the conductor/ground, conductor/shield and shield/ground.
Connect the devices that are operated in hazardous areas as per the stipulations
applicable in the country of operation, e.g. for Ex "d" and "nA", permanent cables must
be laid.
WARNING
Explosion Hazard
Devices with the common approval "Intrinsically safe" and "Flameproof"
The following is applicable for devices with the common approval "Intrinsically safe" and
"Flameproof" (Ex ia + Ex d): Before commissioning, make sure that the type of
protection that is not suitable is permanently defaced on the nameplate to avoid
improper use.
If a non-conforming infeed is used, the "fail-safe" type of protection will no longer be
effective.
Summary of Contents for FUG1010 IP65 NEMA 4X
Page 9: ...Table of contents FUG1010 IP65 NEMA 4X 8 Operating Instructions 01 2013 A5E02951519 AC ...
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ...21614 C 1011NFPS 7 ...
Page 238: ...1011NFPS 7 C 21614 ...
Page 239: ...1011NFPS 7 C 21614 ...
Page 240: ...21614 C 1011NFPS 7 ...
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ...21614 C ...
Page 247: ......
Page 248: ......
Page 249: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 250: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 251: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 252: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 253: ......
Page 254: ......
Page 255: ......
Page 256: ......
Page 257: ......
Page 258: ......
Page 266: ...Glossary FUG1010 IP65 NEMA 4X 200 Operating Instructions 01 2013 A5E02951519 AC ...
Page 270: ...Index FUG1010 IP65 NEMA 4X 204 Operating Instructions 01 2013 A5E02951519 AC ...