 Channel 4 - input/output 

 Frequency output 

 Fail-safe 

minimum time 

3.4.3.3.10 Fail-safe value 

Description 
Output value in case of a fault and when fail-safe mode configured to fail-safe value. 

 

Setting  0.0 Hz to 12500.0 Hz 
Default  0.0 Hz 

Related 

 

Path 

Setup 

 Inputs and outputs 

 Channel 4 - input/output 

 Frequency output 

 Fail-safe 

value 

3.4.4.4

 

Pulse output 

3.4.3.4.1 Process value 

Description 
Select process value for the pulse output. 

 

Setting  Mass flow; Volume flow 
Default  Volume flow 

Related 

 

Path 

Setup 

 Inputs and outputs 

 Channel 4 - input/output 

 Pulse output 

 Process value 

3.4.3.4.2 Direction 

Description 
Flow direction filter. 

 

Setting  Positive; Negative; Bidirectional; Bidirectional (symmetric) 
Default  Positive 

Related 

 

Path 

Setup 

 Inputs and outputs 

 Channel 4 - input/output 

 Pulse output 

 Direction 

Summary of Contents for FST020

Page 1: ...Function manual Answers for industry 09 2017 Edition Ultrasonic Flowmeters FST020 IP65 NEMA 4X SITRANS F ...

Page 2: ......

Page 3: ...RANS F Ultrasonic Flowmeters FST020 Function manual Function Manual 09 2017 A5E42949526 AA Introduction 1 Quick start 2 Setup 3 Maintenance and diagnostics 4 Communication 5 Security 6 Language 7 Support A ...

Page 4: ...ay be operated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WAR...

Page 5: ... 3 1 Sensor settings 19 3 1 1 Length unit 19 3 1 2 Length unit settings 19 3 1 3 Pipe settings 19 3 1 3 1 Pipe class 19 3 1 3 2 Pipe size 19 3 1 3 3 Outer pipe diameter 20 3 1 3 4 Wall thickness 20 3 1 3 5 Pipe material 20 3 1 3 6 Wall sound velocity 20 3 1 3 7 Liner settings 21 3 1 3 8 Inner pipe roughness 22 3 1 3 9 Inner pipe diameter 22 3 1 4 Upstream and downstream conditions 22 3 1 4 1 Distu...

Page 6: ...User calibration 32 3 1 8 1 Slope 32 3 1 8 2 Path 1 offset 32 3 1 9 Multipoint calibration 33 3 1 9 1 Enable multipoint calibration 33 3 1 9 2 Asymmetric calibration table 33 3 1 9 3 Calibration point 34 3 1 9 4 Multipoint calibration table 34 3 1 10 Flow direction 35 3 1 11 Miscellaneous 35 3 1 11 1 Preamplifier Setting 35 3 1 11 2 Number of pulses to be transmitted 36 3 1 11 3 Minimum ringdown d...

Page 7: ...ity 53 3 2 6 1 Units 53 3 2 6 2 Decimal places 53 3 2 6 3 Alarm and warning limits 53 3 2 7 Medium temperature 55 3 2 7 1 Units 55 3 2 7 2 Decimal places 55 3 2 7 3 Alarm and warning limits 55 3 3 Totalizers 57 3 3 1 Totalizer 1 57 3 3 1 1 Process value 57 3 3 1 2 Units 58 3 3 1 3 Custom units 58 3 3 1 4 Custom conversion factor 58 3 3 1 5 Decimal places 59 3 3 1 6 Direction 59 3 3 1 7 Fail safe b...

Page 8: ...81 3 4 4 4 Pulse output 84 3 4 5 Channel 7 digital input 88 3 4 5 1 Input function 88 3 4 6 Channel 8 digital input 88 3 4 6 1 Input function 88 3 4 6 2 Input function settings 88 3 5 Date and time 88 3 5 1 Current date and time 88 3 5 2 Set date and time 89 3 6 Local display 89 3 6 1 FST020 Display 89 3 6 2 Brightness 90 3 6 3 Backlight 90 3 6 4 Contrast 90 3 7 Damping 91 3 7 1 Damping value 91 3...

Page 9: ...th process value 103 3 10 9 6th process value 103 3 10 10 Trend scale mode 104 3 10 11 Trend log time window 104 3 10 12 Trend scale lower limit 104 3 10 13 Trend scale upper limit 105 3 11 View 4 105 3 11 1 Enable or disable 105 3 11 2 View 105 3 11 3 1st value 106 3 11 4 2nd value 106 3 11 5 3rd value 107 3 11 6 4th value 107 3 11 7 5th value 108 3 11 8 6th value 108 3 11 9 Trend scale mode 108 ...

Page 10: ...ge 122 4 1 5 Location 122 4 1 6 Installation date 122 4 1 7 Manufacturer 122 4 1 8 Product name 123 4 1 9 Version read only 123 4 1 10 Order number read only 123 4 1 11 Serial number 123 4 1 12 FW version 124 4 1 13 HW version 124 4 1 14 Final assembly number 124 4 1 15 System type 125 4 1 16 Transmitter electronics 125 4 1 16 1 HW version 125 4 1 16 2 FW version 125 4 1 16 3 Serial number 125 4 1...

Page 11: ...5 4 2 8 3 149 Transm temp below alarm limit 136 4 3 Maintenance 136 4 3 1 Copy configuration 136 4 3 2 Spare part replacement 136 4 3 2 1 Transmitter 136 4 3 2 2 Operating time 137 4 3 3 Electronic part identification 137 4 3 3 1 Transmitter cassette 137 4 3 3 2 Local display 139 4 3 3 3 I O cassette 140 4 3 3 4 Sensor cassette 140 4 4 Diagnostics 141 4 4 1 Sensor 141 4 4 1 1 Receiver signal 141 4...

Page 12: ...minimum 155 4 5 4 6 Reset peak values 155 4 6 Characteristics 155 4 6 1 Transmitter 155 4 6 1 1 Design read only 155 4 7 SensorFlash 156 4 7 1 Eject 156 4 7 2 Installed read only 156 4 7 3 Capacity total read only 156 4 7 4 Capacity available read only 157 4 7 5 Data logging 157 4 7 5 1 Activation 157 4 7 5 2 Data logging mode 157 4 7 5 3 Logging interval 158 4 7 5 4 Process values 158 4 8 Simulat...

Page 13: ...e 173 5 1 3 MSD connect write only 173 5 2 Modbus Channel 1 174 5 2 1 Slave address SW 174 5 2 2 Slave address HW read only 174 5 2 3 Baud rate 174 5 2 4 Parity framing 175 5 2 5 Floating point byte order 175 5 2 6 Integer byte order 175 5 2 7 Register mapping 176 5 2 7 1 Enable mapping 176 5 2 7 2 Source register 1 20 176 5 2 7 3 Target register 1 20 176 5 2 8 Modbus units 177 5 2 8 1 Mass flow u...

Page 14: ...0 Function manual 12 Function Manual 09 2017 A5E42949526 AA 6 6 Deactivate user PIN 182 6 7 Auto logout 182 6 8 Auto logout 183 6 9 Logout 183 7 Language 185 7 1 Language 185 A Support 187 A 1 Technical support 187 Index 189 ...

Page 15: ...re the relation if any between parameters is described As of chapter 3 Setup Page 19 the chapter and subchapter numbers equal the parameter numbers in the HMI structure For parameters with access level other than User for example Read only or Expert the access level is stated in parenthesis after the parameter name 1 3 Quick start wizards The device offers a set of wizards which will guide you thr...

Page 16: ...dition are given in the following table Edition Note 09 2017 First edition 1 7 Device documentation package The user documentation package for this product includes the following documents Document Purpose Intended users Availability Application plan ning sheets Contains all information needed to plan the mechanical physical installation and control signals before the product ar rives Plant design...

Page 17: ...echanical and electrical install ers instrument technicians Included in the delivery On documentation disk Available for download from homepage Functions Manual Contains descriptions of all functions that can be accessed via the local display HMI guide to setting parameters to obtain opti mum operation of the device Instrument tech nicians plant operators Available for download from homepage Hardc...

Page 18: ...Introduction 1 7 Device documentation package FST020 Function manual 16 Function Manual 09 2017 A5E42949526 AA ...

Page 19: ...ration path and sub wizards appropriate for your application 2 3 Sensor settings Description The sensor settings wizard will guide you through configuration of essential parameters 2 4 Process values The Process values wizard will guide you through setup of process values for your application The prioritizing of the process values automatically configures the measurement views on the display The p...

Page 20: ...Quick start 2 6 Copy configuration FST020 Function manual 18 Function Manual 09 2017 A5E42949526 AA ...

Page 21: ... Sensor settings Length units 3 1 3 Pipe settings 3 1 3 1 Pipe class Description Pipe class Read only Can only be changed via the Sensor Wizard Indicates the pipe class chosen from the pipe data library included in the sensor setup wizard 3 1 3 2 Pipe size Description Pipe size Read only Can only be changed via the Sensor Wizard Indicates the pipe class chosen from the pipe data library included i...

Page 22: ...pe material Description Pipe material Read only Can only be changed via the Sensor Wizard Setting Read only Carbon steel Stainless steel ABS plastic Aluminum Black iron Brass Cast iron Copper nickel 70 30 Copper nickel 90 10 Copper Ductile iron FRP plastic Glass Hastelloy Inconel Kynar plastic Monel Nickel Polyethylene PVC plastic Teflon Titani um Default Can only be changed via the Sensor wizard ...

Page 23: ... m Default 0 0 m Related Path Setup Sensor settings Pipe settings Liner settings Liner thickness 3 1 3 7 2 Liner material Description Liner material Read only Can only be changed via the Sensor Wizard Setting Read only Custom Cement Coal tar Enamel Glass Plastic Hi_dens_Poly PTFE Rub ber Default Custom Related Path Setup Sensor settings Pipe settings Liner settings Liner material 3 1 3 7 3 Liner s...

Page 24: ... settings Pipe settings Inner pipe roughness 3 1 3 9 Inner pipe diameter Description Read only Calculated inner diameter of pipe clamp on Setting Default 0 0 m Related Path Setup Sensor settings Pipe settings Inner pipe diameter 3 1 4 Upstream and downstream conditions 3 1 4 1 Disturbed flow profile compensation Description Disturbed flow profile compensation enable disable Setting Enable Disabled...

Page 25: ...tream flow disturbance The distance is given in pipe diameters Used for clamp on flow profile compensation Setting 0 to 40 Default 0 Related Path Setup Sensor settings Upstream and downstream conditions Upstream distance 3 1 4 4 Type of downstream condition Description Compensation for downstream pipe geometry Setting Straight run Single elbow Double elbow in plane Double elbow out of plane Reduce...

Page 26: ...a the Sensor Wizard Indicates the fluid medium type chosen from the fluid data library included in the sensor setup wizard 3 1 5 2 Expected sound velocity Description Expected sound velocity in the medium at process temperature Setting 100 0 m s to 2500 0 m s Default 1500 0 m s Related Path Setup Sensor settings Fluid settings Expected sound velocity 3 1 5 3 Process temperature Description Tempera...

Page 27: ...tion Input during setup Setting 0 0 kg m to 2000 0 kg m Default 1000 0 kg m Related Path Setup Sensor settings Medium characteristics Process density 3 1 6 Sensor selection 3 1 6 1 Sensor model Description Installed sensor model for multi path all must be the same Read only Can only be changed via the Sensor Wizard Indicates the Sensor model chosen from the sensor setup wizard Setting Read only FS...

Page 28: ...etup Sensor settings Sensor selection Nominal sensor frequency 3 1 6 4 Sensor crystal projection Description Length of the crystal projection onto the emitting surface of the sensor clamp on Access level Expert user only Setting 0 0 m to 0 3 m Default 0 03409 m Related Path Setup Sensor settings Sensor settings Sensor crystal projection 3 1 6 5 Sensor phase velocity Description The velocity at whi...

Page 29: ...or fixed time Description Fixed time in sensor wedge Access level Expert user only Setting 2 0 x 10 6 s to 200 0 x 10 6 s Default 10 61 x 10 6 s Related Path Setup Sensor settings Sensor settings Sensor fixed time 3 1 6 8 Mounting hole offset Description Distance between spacer hole and sensor front face Setting 0 0 m to 0 05 m Default 0 00953 m Related Path Setup Sensor settings Sensor settings M...

Page 30: ...r selection Temperature code of the sensor 3 1 6 11 Temperature compensation factor Description Temperature compensation factors for the sensors Setting 0 0001 to 0 0009 Default 0 000638 Related Path Setup Sensor settings Sensor selection Temperature compensation factor 3 1 6 12 Length of sensor cables Description Length of sensor cable between transmitter DSL and any sensors All cables must have ...

Page 31: ...ings Path settings Installed paths 3 1 7 2 Path 1 3 1 7 2 1 Sensor frequency Description Desired sensor frequency for path 1 Read only Setting 80000 0 Hz to 4000000 0 Hz Default Related Path Setup Sensor settings Path settings Path 1 Sensor frequency 3 1 7 2 2 Path geometry Description The number of crossings the signal makes through the pipe Reflect or Direct geometry for Path 1 For example Direc...

Page 32: ...ath Setup Sensor settings Path settings Path 1 Sensor spacing 3 1 7 2 4 Zero point adjustment Description Zero point adjustment Can only be changed via the Sensor Wizard Note Important Please stop all flow in the pipe and perform this function The flow velocity is measured prior and after the function has been applied Setting 5 to 300 Default 10 Related Path Setup Sensor settings Path settings Pat...

Page 33: ...Path Setup Sensor settings Path settings Path diagnostic alarm limits Percent bursts accepted alarm limit 3 1 7 3 2 Correlation factor alarm limit Description Sets the desired limit for the correlation factor If the measured correlation factor drops below this limit for any installed path an alarm will be issued Setting Min 0 0 Max 1 0 Default 0 95 Related Path Setup Sensor settings Path settings ...

Page 34: ...Min 0 0 dB Max 100 dB Default 20 dB Related Path Setup Sensor settings Path settings Path diagnostic alarm limits SNR alarm limit 3 1 8 User calibration 3 1 8 1 Slope Description A single point flow correction applied to volume flow equally at any flow rate Q Q Slope e g Slope of 0 99 1 correction Setting 0 5 to 2 0 Default 1 0 Related Path Setup Sensor settings User calibration Slope 3 1 8 2 Path...

Page 35: ...table Description Note Access level Expert user only Only available for LUILOCAL_CURRENT_LUI_ACCESS_LEVEL SUP AND PID_ProtectCalibrationTable 0 AND PID_EnableUserCalibrationTable 1 Usage of the calibration table Unidirectional All 20 calibration points are used for positive flow calibration and are then mirrored for negative flow Bidirectional The first 10 calibration points are used for positive ...

Page 36: ...ts 1 through 20 for unidirectional flow or calibration points 1 through 20 for bidirectional positive flow If 0 0 the calibration point is not used Access level Expert user only Note Only available for PID_ProtectCalibrationTable 1 OR PID_EnableUserCalibrationTable 1 Setting 0 0 m3 s to 100000 0 m3 s Default 0 0 m3 s Related Path Setup Sensor settings Multipoint calibration Multipoint calibration ...

Page 37: ...n Default positive flow direction is indicated by the arrow on the sensor Setting Negative Positive Default Positive Related Path Setup Sensor settings Flow direction 3 1 11 Miscellaneous 3 1 11 1 Preamplifier Setting Description Preamplifier settings Access level Expert user only Auto default Will automatically turn on the pre amplifier if the sensor type is clamp on Off Turns off the pre amplifi...

Page 38: ...10 Default 5 Related Path Setup Sensor settings Miscellaneous Number of pulses to be transmitted 3 1 11 3 Minimum ringdown delay Description The minimum ringdown delay is needed for optimized signal processing Access level Expert user only Read only The minimum ringdown delay setting for optimized signal processing is 2000 000122 μs 3 1 11 4 Electronic time delay Description The time delay induced...

Page 39: ...onfiguration data is needed Back up and record data as necessary The wizard configures the device for use with the Siemens sensor test blocks including sensor size and sensor path It also allows for saving the setting 3 1 12 2 Sensor size Sensor size Sensor path A1 Path 1 Path 2 A2 Path 1 Path 2 B1 Path 1 Path 2 B2 Path 1 Path 2 B3 Path 1 Path 2 C1 Path 1 Path 2 C2 Path 1 Path 2 C3 Path 1 Path 2 D...

Page 40: ... d 1 barrel 31 US gallons BBL42 s 1 barrel 42 US gallons BBL42 min 1 barrel 42 US gallons BBL42 h 1 barrel 42 US gallons BBL42 d 1 barrel 42 US gallons KBBL42 d Thousand barrels per day MBBL42 d million barrels per day BBL31 5 s 1 barrel 31 5 US gallons BBL31 5 min 1 barrel 31 5 US gallons BBL31 5 h 1 barrel 31 5 US gallons BBL31 5 d 1 barrel 31 5 US gallons ft s cubic feet per second ft min cubic...

Page 41: ...ription Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Standard volume flow Decimal places 3 2 1 5 Low flow cut off Description Volume flow limit for low flow cut off Below limit v...

Page 42: ... limit 3 2 1 6 2 Upper warning limit Description Exceeding this limit causes a warning Setting 896 40 m3 h to 896 40 m3 h Default 896 40 m3 h Related Path Setup Process values Volume flow Alarm and warning limits Upper warning limit 3 2 1 6 3 Lower warning limit Description Falling below this limit causes a warning Setting 896 40 m3 h to 896 40 m3 h Default 896 40 m3 h Related Path Setup Process v...

Page 43: ... 2 2 Mass flow 3 2 2 1 Units Description Select units for displayed mass flow rate Units are not applied at communication interface Setting g s grams per second g min grams per min g h grams per hour kg s kilograms per second kg min kilograms per minute kg h kilograms per hour kg d kilograms per day t min 1 t 1000 kg t h 1 t 1000 kg t d 1 t 1000 kg STon min 1 STon 2000 lb STon h 1 STon 2000 lb STo...

Page 44: ...Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Mass flow Decimal places 3 2 2 5 Low flow cut off Description Mass flow limit for low flow cut off Below limit mass flow ...

Page 45: ...r warning limit Description Exceeding this limit causes a warning Setting 3682800 00 kg h to 3682800 00 kg h Default 3682800 00 kg h Related Path Setup Process values Mass flow Alarm and warning limits Upper warning limit 3 2 2 6 3 Lower warning limit Description If the mass flow value falls below this limit a warning is triggered Setting 3682800 00 kg h to 3682800 00 kg h Default 3682800 00 kg h ...

Page 46: ...h Related Path Setup Process values Mass flow Alarm and warning limits Hysteresis 3 2 3 Flow velocity 3 2 3 1 Units Description Select units for displayed flow velocity Units are not applied at communication interface Units for flow velocity values Setting m s meters per second m h meters per hour in s inches per second in min inches per minute ft s feet per second ft min feet per minute custom un...

Page 47: ...conversion factor 3 2 3 4 Decimal places Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Flow velocity Decimal places 3 2 3 5 Low flow cut off Description Flow velocity ...

Page 48: ...limits Description If process value exceeds this limit a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Flow velocity Alarm and warning limits Upper warning limit 3 2 3 6 3 Lower warning limit Description If process value falls below this limit a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 ...

Page 49: ...rning limits Hysteresis Setting 0 m s to 9999997952 m s Default 0 00 m s Related Path Setup Process values Flow velocity Alarm and warning limits Hysteresis 3 2 4 Sound velocity 3 2 4 1 Units Description Select units for displayed sound velocity Units are not applied at communication interface Setting m s meters per second m h meters per hour in s inches per second in min inches per minute ft s fe...

Page 50: ...t sound velocity values based on SI velocity units m s Setting Default 1 0 Related Path Setup Process values Sound velocity Custom conversion factor 3 2 4 4 Decimal places Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default ...

Page 51: ...ed Path Setup Process values Sound velocity Alarm and warning limits Upper warning limit 3 2 4 5 3 Lower warning limit Description if the process value falls below this limit a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Sound velocity Alarm and warning limits Lower warning limit 3 2 4 5 4 Lower alarm limit Description If t...

Page 52: ...cation interface Read only Setting μg l micrograms per liter μg m micrograms per cubic meter mg l milligrams per liter g ml grams per milliliter g cm grams per cubic centimeters g l grams per liter kg l kilograms per liter kg m kilograms per cubic meter lb in pounds per cubic inch lb gal pounds per US gallon lb ft pounds per cubic foot STon yd 1 STon 2000 lb custom units see Custom units Custom co...

Page 53: ...e local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Density Decimal places 3 2 5 5 Alarm warning limits 3 2 5 5 1 Upper alarm limit Description If density value exceeds this limit an alarm is triggered Setting 0 00 kg m to 10000 00 kg m Default 9...

Page 54: ...s values Density Alarm and warning limits Lower warning limit 3 2 5 5 4 Lower alarm limit Description If density value falls below this limit an alarm is triggered Setting 0 00 kg m to 10000 00 kg m Default 1 00 kg m Related Path Setup Process values Density Alarm and warning limits Lower alarm limit 3 2 5 5 5 Hysteresis Description Sets the hysteresis for alarm and warning limits The hysteresis i...

Page 55: ...ets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Kinematic viscosity Decimal places 3 2 6 3 Alarm and warning limits 3 2 6 3 1 Upper alarm limit Description If process value exceeds t...

Page 56: ...it a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Kinematic viscosity Alarm and warning limits Lower warning limit 3 2 6 3 4 Lower alarm limit Description If process value falls below this limit an alarm is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Kinematic v...

Page 57: ...s Celsius F degrees Fahrenheit R degrees Rankine K kelvins Default C degrees Celsius Related Path Setup Process values Medium temperature Units 3 2 7 2 Decimal places Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 dec...

Page 58: ...s limit causes a warning Related Setting 272 77 to 400 00 C Default 270 00 C Related Path Setup Process values Medium temperature Alarm and warning limits Upper warn ing limit 3 2 7 3 3 Lower warning limit Description Falling below this limit causes a warning Setting 272 77 00 to 400 00 C Default 270 00 C Related Path Setup Process values Medium temperature Alarm and warning limits Lower warn ing ...

Page 59: ...eresis for alarm and warning limits The hysteresis is the distance between the limits for activation and deactivation of an alarm warning Setting 0 00 C to 200 00 C Default 0 00 C Related Path Setup Process values Medium temperature Alarm and warning limits Hysteresis 3 3 Totalizers 3 3 1 Totalizer 1 3 3 1 1 Process value Description Select the process value to be totalized Setting Mass flow Volum...

Page 60: ...allons BBL42 1 barrel 42 US gallons in cubic inches ft cubic feet yd cubic yards bush bushels Process value Standard volume flow Nl normal liters Nm normal cubic meters Sl standard liters Sft standard cubic feet Sm standard cubic meters custom units see Custom units Custom conversion factor Default kg kilograms Related Path Setup Totalizers Totalizer 1 Units 3 3 1 3 Custom units Description User s...

Page 61: ... Description Totalizer 1 direction Setting Forward and backward Forward Backward Hold Default Forward Related Path Setup Totalizers Totalizer 1 Direction 3 3 1 7 Fail safe behaviour Description Behaviour of the totalizer during the occurrence of bad input value Setting RUN totalization is continued using the bad input value HOLD totalization is stopped MEMORY totalization is continued based on the...

Page 62: ...7952 m to 9999997952 m Setting Cancel OK Default Cancel Related Path Setup Totalizers Totalizer 1 Preset 3 3 1 10 Alarm and warning limits 3 3 1 10 1 Upper alarm limit Description Alarm is triggered if Totalizer 1 value is above the limit Setting Process value Mass flow 9999997952 kg to 9999997952 kg Process value Volume flow 9999997952 m to 9999997952 m Default Process value Mass flow 9999997952 ...

Page 63: ... 9999997952 m to 9999997952 m Default Process value Mass flow 9999997952 kg Process value Volume flow 9999997952 m Related Path Setup Totalizers Totalizer 1 Alarm and warning limits Lower warning limit 3 3 1 10 4 Lower alarm limit Description Alarm is triggered if Totalizer 1 value is below the limit Setting Process value Mass flow 9999997952 kg to 9999997952 kg Process value Volume flow 999999795...

Page 64: ...f input and output is described in the following table Table 3 1 Hardware and software configuration of the input output channels Channel HW configuration fixed when ordering SW configuration available to the user 1 Modbus Modbus 2 Signal output Outputs Current output 0 4 20 mA 3 Relay output Status Output Alarm class Alarm item NAMUR status signals 4 Signal input output Outputs Frequency ouput Pu...

Page 65: ...lt current value Recommended setting range for lower fault current Recommended setting range for upper fault current Measuring range Figure 3 1 Current limits for NAMUR configuration The fail safe current output signal can be selected to Lower fault current defined in the Loop current scale selection Upper fault current defined in the Loop current scale selection Last valid value the last process ...

Page 66: ...cut off Upper range value Maximum output current Upper fault current Lower range value Lower saturation limit Span Current output setting Process value Mass flow Direction Positive Loop current scale 4 20 mA maximum 25 mA Upper range value 100 kg h Lower range value 400 kg h Fail safe behaviour Upper fault current Low flow cut off 25 kg h ...

Page 67: ...ower range value Low flow cut off Upper range value Upper saturation limit Lower saturation limit Lower fault current Span Current output setting Process value Mass flow Direction Bidirectional Loop current scale 4 20 mA NAMUR Upper range value 400 kg h Lower range value 100 kg h Fail safe behaviour Upper fault current Low flow cut off 25 kg h ...

Page 68: ...ling Lower range value Low flow cut off Upper range value Upper saturation limit Lower saturation limit Lower fault current Span Current output setting Process value Mass flow Direction Bidirectional Loop current scale 4 20 mA US Upper range value 400 kg h Lower range value 100 kg h Fail safe behaviour Minimum current Low flow cut off 25 kg h ...

Page 69: ... Process value Mass flow Direction Bidirectional Symmetric Loop current scale 4 20 mA NAMUR Upper range value 400 kg h Lower range value 100 kg h Fail safe behaviour Upper fault current Low flow cut off 25 kg h Pulse output The pulse output function supplies pulses equivalent to a configured amount of accumulated volume or mass The pulse width is configured and the pulse repetition is proportional...

Page 70: ...ms Note Pulse width must be selected with the view that remaining time is always greater than pulse width at the highest measured flow Frequency output The frequency output function supplies a frequency 50 duty cycle proportional to the selected process value Frequency is calculated as follows Example This example shows how to calculate the output frequency for any measured flowrate Frequency outp...

Page 71: ...ess value to 0 A warning will occur in case of negative flow This warning can be output on the status output if Status mode is set to Alarm item and the Process alarms 1 relevant process value below warning limit is selected 3 4 1 Alarm status Depending on the Status mode setting multiple alarms can be signaled on the output and selected from the alarm class or the alarm item lists Alarm class Ala...

Page 72: ...n the input is inactive Note Changing polarity Changing the polarity triggers the signal input to execute the set functionality 3 4 2 Channel 2 output 3 4 2 1 Operation mode Description Operation mode Sets the output functionality for channel operation Setting Off Current output Default Off Related Path Setup Inputs and outputs Channel 2 output Operation mode 3 4 2 2 Active operation read only Des...

Page 73: ...3 4 2 4 Current output 3 4 3 4 1 Process value Description Select process value for the current output Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Medi um temperature Default Mass flow Related Path Setup Inputs and outputs Channel 2 output Current output Process value 3 4 3 4 2 Direction Description Flow direction filter applicable for process values mass...

Page 74: ...NAMUR Related Path Setup Inputs and outputs Channel 2 output Current output Loop current scale 3 4 3 4 4 Upper range value Description Sets value at 100 of measuring span and corresponds to a loop current of 20 mA Setting and Default are sensor specific depending on the setting in Process value and depending on the Units setting Setting 3682800 00 kg h to 3682800 00 kg h Default 3682800 00 kg h Re...

Page 75: ...requirements of signal stability and response time Setting 0 00 s to 100 00 s Default 0 00 s Related Path Setup Inputs and outputs Channel 2 output Current output Damping value 3 4 3 4 7 Fail safe behaviour Description Current output reaction in case of a fault Setting Lower fault current Upper fault current Last valid value Current value Fail safe value Default Lower fault current Related Path Se...

Page 76: ...ff delay Description Set the time delay between resetting alarm condition and de activating the output Setting 0 0 s to 100 0 s Default 0 0 s Related Path Setup Inputs and outputs Channel 2 output Status output Off delay 3 4 3 Channel 3 relay 3 4 3 1 Operation mode Description Select the operation mode for the relay output Setting Alarm class Alarm item Default Alarm class Related Path Setup Input...

Page 77: ...07 Flow measurement 08 DSL internal 14 Path 1 No signal 26 Sensor temp comp 28 Default None Related Path Setup Inputs and outputs Channel 3 relay Sensor alarms 1 3 4 3 4 Sensor alarms 2 Description Selection of alarm items that impact the output Mainly sensor alarms Applicable if Status mode Alarm item Setting 34 Invalid flow meas 36 Configuration 2 37 DSL system monitor Default None Related Path ...

Page 78: ...ion of alarm items that impact the output Applicable if Status mode Alarm item For hydrocarbon and gas applications only Setting 228 Sound velocity above alarm limit 229 Sound velocity above warning limit 230 Sound velocity below warning limit 231 Sound velocity below alarm limit 232 Flow velocity above alarm limit 233 Flow velocity above warning limit 234 Flow velocity below warning limit 235 Flo...

Page 79: ...uts Channel 3 relay Totalizer alarms 3 4 3 9 Device alarms Description Device alarms If one of the selected events appears this affects the status icon the related status output and the alarm on the communication interface Setting 148 Transm temp above alarm limit 149 Transm temp below alarm limit 150 Sensor signal disrupted 159 Internal error in transmitter Default None Related Path Setup Inputs ...

Page 80: ...s Channel 3 relay Input output alarms 3 4 3 11 Simulation alarms 1 Description Selection of alarm items that impact the output Mainly simulation alarms Applicable if Status mode Alarm item Setting 160 Mass flow simulated 161 Volume flow simulated 162 Density simulated 163 Medium temp simulated 167 Totalizer 1 simulated Default None Related Path Setup Inputs and outputs Channel 3 relay Simulation a...

Page 81: ...arm Process value warning Mainte nance demanded Maintenance required None Default Related Path Setup Inputs and outputs Channel 3 relay Alarm class 3 4 3 14 NAMUR status signal Description Selection of NAMUR status signals which impact the status output Each diagnostic event is allocated to a NAMUR status signal Application if Status mode Alarm class and Status icons NAMUR Setting Failure Function...

Page 82: ...3 4 3 17 Off delay Description Set the time delay between resetting alarm condition and de activating the output Setting 0 0 s to 100 0 s Default 0 0 s Related Path Setup Inputs and outputs Channel 3 relay Off delay 3 4 4 Channel 4 input output 3 4 4 1 Operation mode Description Shows the configured Operation mode Use Change operation mode to set the mode Read only Setting Off Frequency output Pul...

Page 83: ...quency output Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Medi um temperature Default Volume flow Related Path Setup Inputs and outputs Channel 4 input output 4 Frequency output Process value 3 4 3 3 2 Direction Description Flow direction filter applicable for process values mass flow volume flow flow velocity standard volume flow rate only hydrocarbon an...

Page 84: ... 0 Hz to 12500 0 Hz Default 0 0 Hz Related Path Setup Inputs and outputs Channel 4 input output Frequency output Frequency value low 3 4 3 3 5 Upper range value Description Sets value at 100 of measuring span and corresponds to Frequency value high Setting and Default are sensor specific depending on the setting in Process value and depending on the Units setting Setting 10800000000 00 kg h to 108...

Page 85: ...e constant of damping filter for frequency output signal Setting 0 0 s to 100 0 s Default 0 0 s Related Path Setup Inputs and outputs Channel 4 input output Frequency output Damping value 3 4 3 3 8 Fail safe behaviour Description Frequency output reaction in case of a fault Setting Minimum frequency Maximum frequency Last valid value Current valid fail safe value Default Last valid value Related P...

Page 86: ... 0 0 Hz Related Path Setup Inputs and outputs Channel 4 input output Frequency output Fail safe value 3 4 4 4 Pulse output 3 4 3 4 1 Process value Description Select process value for the pulse output Setting Mass flow Volume flow Default Volume flow Related Path Setup Inputs and outputs Channel 4 input output Pulse output Process value 3 4 3 4 2 Direction Description Flow direction filter Setting...

Page 87: ...0 lb T 1 T 2240 lb oz ounces lb pounds custom units see Custom units Custom conversion factor Default I liters Related Path Setup Inputs and outputs Channel 4 input output Pulse output Pulse units 3 4 3 4 4 Custom units Description User specific string to define custom pulse units Setting Default Related Path Setup Inputs and outputs Channel 4 input output Pulse output Custom units 3 4 3 4 5 Custo...

Page 88: ... 1 Related Path Setup Inputs and outputs Channel 4 input output Pulse output Pulses per amount 3 4 3 4 8 Pulse width units Description Units of pulse duration value used to configure Ch4 pulse width Setting s seconds ms milliseconds μs micro seconds Default s seconds Related Path Setup Inputs outputs Channel 4 input output Pulse output Pulse width units 3 4 3 4 9 Polarity Description Logical polar...

Page 89: ...output Fail safe behav iour 3 4 3 4 11 Fail safe value Description Output value in case of a fault and when fail safe behaviour configured to Fail safe value Setting 0 0 pulses s to 12500 0 pulses s Default 1 0 pulses s Related Path Setup Inputs and outputs Channel 4 input output Pulse output Fail safe value 3 4 3 4 12 Fail safe minimum time Description Minimum time the output stays in fail safe m...

Page 90: ...d Path Setup Inputs and outputs Channel 7 digital input Input function 3 4 6 Channel 8 digital input 3 4 6 1 Input function Description Shows the digital input function Selects the signal input functionality 3 4 6 2 Input function settings Setting Off Start Stop totalizer 1 on level Default Off Related Path Setup Inputs and outputs Channel 8 digital input Input function 3 5 Date and time 3 5 1 Cur...

Page 91: ... all timestamps of logged information Setting Default Related Path Setup Date and time Set date and time 3 6 Local display 3 6 1 FST020 Display The system can be configured to show up to six different views In view 1 only measurement or diagnostic views can be selected In views 2 to 6 all view types can be selected Measurement views Single value Three values 1 value and bargraph 1 value and graph ...

Page 92: ...0 50 60 70 80 90 100 Default 50 Related Path Setup Local display Brightness 3 6 3 Backlight Description Select between always on or backlight switch off after 10 minutes Setting Automatic Always on Default Automatic 30 s Related Path Setup Local display Backlight 3 6 4 Contrast Description Adjust contrast to improve local display conditions Setting 0 10 20 30 40 50 60 70 80 90 100 Default 80 Relat...

Page 93: ...vailable process values for the meter Setting Volume flow Mass flow Totalizer 1 Sound velocity Flow velocity Pressure Kinematic viscosity Density Medium temperature Default Related Path Setup Local display Damping Process values 1 3 7 3 Process values 2 Description Available process values for the meter Setting API gravity Standard API gravity Specific gravity Standard specific gravity Rate of cha...

Page 94: ...s value must be configured If 1 value and graph is selected 1st process value Trend scale mode and Trend log time window must be configured If Six values or Six diagnostic values is selected 1st process value 2nd process value 3rd process value 4th process value 5th process value and 6th process value must be configured Path Setup Local display View 1 View 3 8 2 1st value Description The display 1...

Page 95: ...ault Density Related This parameter is only available if View 1 is set to Three values Six values or Six diagnostic values Path Setup Local display View 1 2nd value 3 8 5 3rd value Description The display 3rd process value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Totalizer 2 Totalizer 3 Pressure Medium temperature Default M...

Page 96: ...lay 5th process value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Process viscosity Fluid temperature Totalizer 1 Default Process pressure Related This parameter is only available if View 1 is set to Six values or Six diagnostic values Path Setup Local display View 1 5th process value 3 8 8 6th process value Description The display 6th process value can be se...

Page 97: ...cale mode 3 8 10 Trend log time window Description The Trend log time window logging period time axis length can be selected Setting 1 minute 5 minutes 15 minutes 30 minutes 1 hour 2 hours 3 hours Default 5 minutes Related This parameter is only available if View is set to 1 value and graph Path Setup Local display View 1 Trend log time window 3 8 11 Trend scale lower limit Description The Trend s...

Page 98: ...to Fixed Path Setup Local display View 1 Trend scale upper limit 3 9 View 2 3 9 1 Enable or disable Description In this parameter View 2 can be enabled Setting Disabled Enabled Default Enabled Related If Enabled is selected all parameters for View 2 must be configured Path Setup Local display View 2 Enable or disable 3 9 2 View Description The display View 2 can be configured Setting Single value ...

Page 99: ...3rd process value 4th process value 5th process value and 6th process value must be configured Path Setup Local display View 2 View 3 9 3 1st value Description The display 1st Process Value can be selected This process value is shown in all view types Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Medium temperature Default Volume flow Related P...

Page 100: ...n The display 4th Process Value can be selected Setting Mass flow Volume flow Density Fluid Temperature Totalizer 1 Default Volumeflow Related This parameter is only available if View is set to Six Values or Six Diagnostic Values Path Setup Display View 2 4th Process Value 3 9 7 5th process value Description The display 5th Process Value can be selected Setting Mass flow Volume flow Density Fluid ...

Page 101: ... be selected with automatic scaling or fixed scaling Setting Auto Fixed Default Auto Related This parameter is only available if View is set to Totalizer or 1 Value and Graph If Fixed is selected Trend Scale Lower Limit and Trend Scale Upper Limit must be configured Path Setup Display View 2 Trend Scale Mode 3 9 10 Trend log time window Description The Trend log time window logging period time axi...

Page 102: ...ode is set to Fixed Path Setup Display View 2 Trend Scale Lower Limit 3 9 12 Trend scale upper limit Description The Trend Scale Upper Limit defines the scaling upper limit of the value axis for the fixed mode Setting options Default setting 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path Setup Display View 2 Trend Scale Upper Limit 3 10 View 3 3 10 1 Enable or ...

Page 103: ...ess value and 3rd process value must be configured If Totalizer or 1 value and graph is selected 1st process value Trend scale mode and Trend log time window must be configured If 1 value and bargraph is selected 1st process value must be configured If Six values or Six diagnostic values is selected 1st process value 2nd process value 3rd process value 4th process value 5th process value and 6th p...

Page 104: ...scosity Total izer 1 Medium Temperature Default Flow velocity Related This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Setup Display View 2 2nd Process Value 3 10 6 3rd process value Description The display 3rd Process Value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Med...

Page 105: ...rocess value Description The display 5th Process Value can be selected Setting Mass flow Volume flow Density Fluid Temperature Totalizer 1 Default Totalizer 1 Related This parameter is only available if View is set to Six Values or Six Diagnostic Values Path Setup Display View 3 5th Process Value 3 10 9 6th process value Description The display 6th Process Value can be selected Setting Mass flow V...

Page 106: ...nd Scale Mode 3 10 11 Trend log time window Description The Trend log time window logging period time axis length can be selected Setting 1 Minute 5 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 3 Hours Default 5 Minutes Related This parameter is only available if View is set to Totalizer or 1 Value and Graph Path Setup Display View 3 Trend log time window 3 10 12 Trend scale lower limit Descriptio...

Page 107: ... to Fixed Path Setup Display View 3 Trend Scale Upper Limit 3 11 View 4 3 11 1 Enable or disable Description In this parameter View 4 can be enabled Setting Disabled Enabled Default Enabled Related If Enabled is selected all parameters for View 4 must be configured Path Setup Display View 4 Enable or disable 3 11 2 View Description The display View 4 can be configured Setting Single value Three va...

Page 108: ...nternal temperature Ch3 value Ch4 value Reynolds number RxGain up path 1 RxGain down path 1 SNR up path 1 SNR down path 1 Sound velocity path 1 Flow velocity path 1 Delta time path 1 Travel time up path 1 Travel time down path 1 Correla tion factor path 1 Percentage of bursts accepted path1 Peak amplitude up path 1 Peak amplitude down path 1 Min acc travel time path 1 Min acc travel time path 1 Ma...

Page 109: ...c travel time path 1 Max acc travel time path 1 Default Sound velocity path 1 Related This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Setup Display View 4 3rd Value 3 11 6 4th value Description The display 4th Process Value can be selected Setting Transmitter internal temperature Reynolds number RxGain up path 1 RxGain down path 1 SNR up pat...

Page 110: ... Six Values or Six Diagnostic Values Path Setup Display View 4 5th value 3 11 8 6th value Description The display 6th Process Value can be selected Setting Transmitter internal temperature Reynolds number RxGain up path 1 RxGain down path 1 SNR up path 1 SNR down path 1 Sound velocity path 1 Flow velocity path 1 Delta time path 1 Travel time up path 1 Travel time down path 1 Correlation factor pat...

Page 111: ...te 5 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 3 Hours Default 5 Minutes Related This parameter is only available if View is set to Totalizer or 1 Value and Graph Path Setup Display View 4 Trend log time window 3 11 11 Trend scale lower limit Description The Trend Scale Lower Limit defines the scaling lower limit of the value axis for the fixed mode Setting Default 0 Related This parameter is o...

Page 112: ...ble 3 12 2 View Description The display View 5 can be configured Setting Single value Three values Totalizer Dosing 1 value and bargraph 1 value and graph Six values Six diagnostic values Alarm list Default Three values Related If Single Value or Dosing is selected 1st Process Value must be configured If Three Values is selected 1st Process Value 2nd Process Value and 3rd Process Value must be con...

Page 113: ...mperature Default Totalizer 1 Related Path Setup Display View 5 1st value 3 12 4 2nd value Description The display 2nd Process Value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Medium temperature Default Density Related This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Set...

Page 114: ...available if View is set to Six Values or Six Diagnostic Values Path Setup Display View 5 4th Process Value 3 12 7 5th process value Description The display 5th Process Value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Medium temperature Default Totalizer 1 Related This parameter is only available if View is set to Six Values ...

Page 115: ...r 1 Value and Graph If Fixed is selected Trend Scale Lower Limit and Trend Scale Upper Limit must be configured Path Setup Display View 5 Trend Scale Mode 3 12 10 Trend log time window Description The Trend log time window logging period time axis length can be selected Setting 1 Minute 5 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 3 Hours Default 5 Minutes Related This parameter is only availabl...

Page 116: ...Upper Limit defines the scaling upper limit of the value axis for the fixed mode Setting options Default setting 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path Setup Display View 5 Trend Scale Upper Limit 3 13 View 6 3 13 1 Enable or disable Description In this parameter View 6 can be enabled Setting Disabled Enabled Default Enabled Related If Enabled is select...

Page 117: ...and Trend log time window must be configured If 1 Value and Bargraph is selected 1st Process Value must be configured If Six Values or Six Diagnostic Values is selected 1st Process Value 2nd Process Value 3rd Process Value 4th Process Value 5th Process Value and 6th Process Value must be configured Path Setup Local display View 6 View 3 13 3 1st process value Description The display 1st Process Va...

Page 118: ...This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Setup Display View 6 3rd Process Value 3 13 6 4th process value Description The display 4th Process Value can be selected Setting Mass flow Volume flow Density Fluid Temperature Totalizer 1 Default Volumeflow Related This parameter is only available if View is set to Six Values or Six Diagnosti...

Page 119: ...Six Values or Six Diagnostic Values Path Setup Display View 6 6th Process Value 3 13 9 Trend scale mode Description The Trend Scale Mode can be selected with automatic scaling or fixed scaling Setting Auto Fixed Default Auto Related This parameter is only available if View is set to Totalizer or 1 Value and Graph If Fixed is selected Trend Scale Lower Limit and Trend Scale Upper Limit must be conf...

Page 120: ...etting Default 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path Setup Display View 6 Trend Scale Lower Limit 3 13 12 Trend scale upper limit Description The Trend Scale Upper Limit defines the scaling upper limit of the value axis for the fixed mode Setting options Default setting 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path...

Page 121: ...Setup 3 14 Status icons FST020 Function manual Function Manual 09 2017 A5E42949526 AA 119 Related Path Setup Local display Status icons ...

Page 122: ...Setup 3 14 Status icons FST020 Function manual 120 Function Manual 09 2017 A5E42949526 AA ...

Page 123: ...nance and diagnostics Identification Long tag 4 1 2 Tag Sets a unique short tag name for device or measurement point Limited to 8 characters Setting User configurable Default characters A B C X Y Z 1 2 3 7 8 9 Related Path Maintenance diagnostics Identification Tag 4 1 3 Descriptor Sets unique description for device Limited to 32 characters Setting User configurable Default 16 characters A B C X Y...

Page 124: ...nique location for device Limited to 32 characters Setting User configurable Default 32 characters A B C X Y Z 1 2 3 7 8 9 Related Path Maintenance and diagnostics Identification Location 4 1 6 Installation date Sets the installation date of the device Setting User configurable Default 16 characters A B C X Y Z 1 2 3 7 8 9 Related Path Maintenance and diagnostics Identification Installation date 4...

Page 125: ...oduct Version according to order can be viewed Setting Default WM int DSL Related Path Maintenance and diagnostics Identification Version 4 1 10 Order number read only Description System order number MLFB can be viewed The system order number consists of three parts Also shown on the device nameplate Setting Default Related Path Maintenance and diagnostics Identification System order number 4 1 11...

Page 126: ...evice Setting Default Related Path Maintenance and diagnostics Identification FW version 4 1 13 HW version Displays version number corresponding to electronics hardware of device Setting Default Related Path Maintenance and diagnostics Identification HW version 4 1 14 Final assembly number Displays number corresponding to materials and components used in final assembly of device Setting 0 to 42949...

Page 127: ...er electronics 4 1 16 1 HW version Displays version number corresponding to electronics hardware of device Setting Default Related Path Maintenance and diagnostics Identification HW version 4 1 16 2 FW version Displays version number corresponding to software or firmware embedded in device Setting Default Related Path Maintenance and diagnostics Identification FW version 4 1 16 3 Serial number Des...

Page 128: ...Maintenance and diagnostics Identification Transmitter Order number 4 1 16 5 Comm interface serial number Description Communication interface serial number Setting Default Related Path Maintenance and diagnostics Identification Transmitter Comm interface serial num ber 4 1 17 Local display Description Local display Setting HW version 1 01 00 Default Setting FW version 1 04 13 09 Default Setting HM...

Page 129: ...Description Displays DSL versions Setting FW version Default Related Path Maintenance and diagnostics Identification DSL 4 1 20 Sensor 4 1 20 1 Type read only Description The name of the digital sensor Path Maintenance and diagnostics Identification Sensor Type 4 1 20 2 Sensor type read only Description Identification of the sensor type Used by the transmitter to enable technology specific functio...

Page 130: ...er 4 1 20 4 Sensor type read only Description Type of sensor Setting SITRANS FSS200 Clamp on SITRANS FSS600 Clamp on Default Related Path Maintenance and diagnostics Identification Sensor Sensor type 4 1 20 5 Sensor firmware version read only Description Sensor firmware version Setting Default Related Path Maintenance and diagnostics Identification Sensor Sensor firmware version 4 1 20 6 Frontend ...

Page 131: ...list of logged events Path Maintenance and diagnostics Diagnostic events Diagnostic log 4 2 3 Clear diagnostic log Description The diagnostic log can be reset using this parameter Setting Cancel OK Default Cancel Related When you confirm the reset by selecting OK the Diagnostic log will be cleared Path Maintenance and diagnostics Diagnostic events Clear diagnostic log 4 2 4 Acknowledge mode Descri...

Page 132: ... DE11 Failed to read FATAL_ERROR_PAGE from DE12 Failed to read SHUT_DOWN_PAGE from DE21 The EEPROM data is inconsistent DE22 Inconsistency of totalizer 1 values DE26 parameter cache full DE27 Unsupported sensor units De28 Communications module not found DE29 Incomplete sensor connected DE30 Invalid sensor type Default Communication module not found Path Maintenance and diagnostics Diagnostic event...

Page 133: ... they will be indicated on the output if Output 2 Input output 3 and or Input output 4 is set to Status output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Sensor events 1 4 2 7 2 Sensor events 2 Description Various sensor alarms can be enabled to show in the display and on the output if they occur Setting 34 Invalid flow meas 36 Configurati...

Page 134: ...cess events 1 4 2 7 4 Process events 2 Description Various sensor alarms can be enabled to show in the display and on the output if they occur Setting Various process alarms selectable Default Related The selected events will be shown in the display when they occur Furthermore they will be indicated on the output if Output 2 Input output 3 and or Input output 4 is set to Status output and Status m...

Page 135: ...ut output 3 and or Input output 4 is set to Status output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Process events 4 4 2 7 7 Totalizer events Description Various sensor alarms can be enabled to show in the display and on the output if they occur Setting 136 Totalizer 1 above alarm limit 137 Totalizer 1 above warning limit 138 Totalizer 1 ...

Page 136: ...vents will be shown in the display when they occur Furthermore they will be indicated on the output if Output 2 Input output 3 and or Input output 4 is set to Status output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Simulation events 1 4 2 7 10 Simulation events 2 Description Various sensor alarms can be enabled to show in the display and ...

Page 137: ...atus output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Input output events 1 4 2 8 Assign alarm class 4 2 8 1 14 Path 1 No signal Description Warning alarms for Path 1 Setting Process value warning Maintenance demanded Maintenance required Default Maintenance required Path Maintenance and diagnostics Diagnostic events Assign alarm class 14...

Page 138: ...ut of specification Path Maintenance and diagnostics Diagnostic events Assign alarm class 149 Transm temp below alarm limit 4 3 Maintenance 4 3 1 Copy configuration Description Copy configuration copy configurations from the SensorFlash to the device Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Copy configuration 4 3 2 Spare part replacement 4 3 2 1 Transmitter 4 3...

Page 139: ...er up Description Operating time total Indicates the total operating time of the transmitter since the last power up 4 3 3 Electronic part identification 4 3 3 1 Transmitter cassette 4 3 3 1 1 HW version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification Transmitte...

Page 140: ...cs Maintenance Electronic part identification Transmitter cassette Serial number 4 3 3 1 4 Comm HW version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification Transmitter cassette Comm HW version 4 3 3 1 5 Comm serial number expert Description Only Siemens authorize...

Page 141: ...t identification Local dis play HW version 4 3 3 2 2 FW version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification Local dis play FW version 4 3 3 2 3 HMI config version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK ...

Page 142: ...tification I O cassette FW version 4 3 3 3 2 Serial number expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification I O cassette Serial number 4 3 3 4 Sensor cassette 4 3 3 4 1 FW version expert Description Only Siemens authorized personnel may replace spare parts Settin...

Page 143: ...onic part identification Sensor cassette Serial number 4 4 Diagnostics 4 4 1 Sensor 4 4 1 1 Receiver signal Description Receiver signal Path Maintenance and diagnostics Diagnostics Sensor Receiver signal 4 4 1 2 Reynolds number read only Description Calculated Reynolds number Path Maintenance and diagnostics Diagnostics Sensor Reynolds number 4 4 1 3 Path 1 4 4 1 3 1 RxGain up read only Descriptio...

Page 144: ...nostics Sensor Path 1 SNR up 4 4 1 3 4 SNR down read only Description Signal to noise ration of downstream signal Path Maintenance and diagnostics Diagnostics Sensor Path 1 SNR down 4 4 1 3 5 Sound velocity read only Description Sound velocity Path Maintenance and diagnostics Diagnostics Sensor Path 1 Sound velocity 4 4 1 3 6 Flow velocity read only Description Flow velocity Path Maintenance and d...

Page 145: ...or Path 1 Travel time down 4 4 1 3 10 Correlation factor read only Description Correlation factor Path Maintenance and diagnostics Diagnostics Sensor Path 1 Correlation factor 4 4 1 3 11 Actual sensor frequency read only Description Sensor frequency Path Maintenance and diagnostics Diagnostics Sensor Path 1 Actual sensor frequency 4 4 1 3 12 Peak amplitude up read only Description Operating time o...

Page 146: ...lue 4 4 2 2 2 Minimum read only Description Drag indicator of minimum transmitter internal temperature Path Maintenance and diagnostics Diagnostics Temperature monitoring Transmitter elec tronics temperature Minimum 4 4 2 2 3 Timestamp at minimum value read only Description Shows timestamp of recorded minimum transmitter internal temperature Path Maintenance and diagnostics Diagnostics Temperature...

Page 147: ...Description The set Operation mode can be viewed in this parameter Options Off Current output Default Current output Related In this parameter the setting of Operation mode is read only Path Maintenance and diagnostics Diagnostics Inputs and outputs Channel 2 output Operation mode 4 4 3 1 2 Status output signal read only Description The channel value can be viewed in this parameter Related if Oper...

Page 148: ... mode is set to Pulse output Related This parameter is only available if Operation mode is set to Current output Frequency output or Pulse output Path Maintenance and diagnostics Diagnostics Inputs and outputs Channel 2 output Error status 4 4 3 2 Channel 3 relay 4 4 3 2 1 Channel 3 relay Description The channel value can be viewed in this parameter Related This parameter is only available if Oper...

Page 149: ...ics Diagnostics Inputs and outputs Channel 4 in put output Channel value 4 4 3 3 3 Error status read only Description The error status of the channel can be viewed in this parameter Options Overflow Underflow Fail safe behaviour is activated Operation mode is set to Frequency output Options The pulse output has reached maximum pulse output frequency Fail safe behaviour is activated Operation mode ...

Page 150: ...s Diagnostics Inputs and outputs Channel 4 in put output Pulse counter 4 4 3 3 5 Reset pulse counter Description The pulse counter can be reset Setting Cancel OK Default Cancel Related This parameter is only available if Operation mode is set to Pulse output Path Maintenance and diagnostics Diagnostics Inputs and outputs Channel 4 in put output Reset pulse counter 4 4 3 4 Calibration picture Descr...

Page 151: ...tamp at maximum value Minimum value Timestamp at Minimum value and Reset logging will be available Path Maintenance and diagnostics Peak values Process value 1 Process value 4 5 1 2 Maximum Displays maximum measured value Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 1 Maximum value 4 5 1 3 Timestamp at m...

Page 152: ... values Process value 1 Minimum value timestamp 4 5 1 6 Reset peak values Description This command is used to reset the logging of the recorded maximum and minimum values monitored The drag pointers will be set to the current value Setting Cancel Ok Default Cancel Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process v...

Page 153: ...tics Peak values Process value 2 Maximum value 4 5 2 3 Timestamp at maximum Displays timestamp when maximum value measured Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 2 Maximum value timestamp 4 5 2 4 Minimum Displays minimum measured value Related This parameter is only available if Process value is no...

Page 154: ... value 3 4 5 3 1 Process value Description Assign the process value to be monitored Setting Disabled Volume flow Mass flow Sound velocity Flow velocity Density Medium temper ature Kinematic viscosity Totalizer 1 Default Disabled Related If this parameter is set to any other setting than Disabled parameters Maximum value Maximum value timestamp Minimum value Minimum value timestamp and Reset loggin...

Page 155: ...h Maintenance and diagnostics Peak values Process value 3 Minimum value 4 5 3 5 Timestamp at minimum Displays timestamp when minimum value measured Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 3 Minimum value timestamp 4 5 3 6 Reset peak values Description This command is used to reset the logging of the...

Page 156: ...ilable Path Maintenance and diagnostics Peak values Process value 4 Assign process value 4 5 4 2 Maximum Displays maximum measured value Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 4 Maximum value 4 5 4 3 Timestamp at maximum Displays timestamp when maximum value measured Related This parameter is only ...

Page 157: ...set peak values Description This command is used to reset the logging of the recorded maximum and minimum values monitored The drag pointers will be set to the current value Setting Cancel Ok Default Cancel Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 4 Reset logging 4 6 Characteristics 4 6 1 Transmitter...

Page 158: ...7 2 Installed read only Description Shows the status of the SD card Setting SensorFlash not installed SensorFlash installed SensorFlash used as mass storage de vice Default SensorFlash installed Related Path Maintenance and diagnostics SensorFlash Installed 4 7 3 Capacity total read only Description Total capacity of installed SensorFlash Shows INSERT CARD if card is not installed Setting Default ...

Page 159: ...tion Description Activation turns on and off data logging activation Setting Off On Default Off Related If this parameter is set to Enabled the parameters Logging value 1 through Logging value 20 can be configured Path Maintenance and diagnostics SensorFlash Data logging Activation 4 7 5 2 Data logging mode Description Select between a momentary value or an averaged value calculated over one loggi...

Page 160: ...h Data logging Logging interval 4 7 5 4 Process values 4 7 5 4 1 Logging value 1 20 Description The process value to be logged can be selected in this parameter Logged process values are an indicator that you have to stop logging before you can change the logged process values Setting Disabled Volume flow Mass flow Sound velocity Flow velocity Density Medium temper ature Kinematic viscosity Totali...

Page 161: ...mulation value Path Maintenance and diagnostics Simulation Simulation inputs and outputs Channel 2 output Operation mode 4 8 1 1 2 Simulation Description Enables or disables simulation of channel 2 current output Setting Disabled Enabled Default Disabled Related Only if this parameter is set to Enabled then the setting of parameter Simulation value will be relevant Path Maintenance and diagnostics...

Page 162: ...on Enables or disables simulation of channel 3 relay output Setting Disabled Enabled Default Disabled Related Only if this parameter is set to Enabled then the setting of parameter Simulation value will be relevant Path Maintenance and diagnostics Simulation Simulation inputs and outputs Channel 3 relay Simulation 4 8 1 2 2 Simulation value Description Relay output value to be output when simulati...

Page 163: ...tput Operation mode 4 8 1 3 2 Simulation Description Enables or disables simulation of Channel 4 input output Setting Disabled Enabled Default Disabled Related Only if this parameter is set to Enabled then the setting of parameter Simulation value will be relevant Path Maintenance and diagnostics Simulation Simulation inputs and outputs Channel 4 input output Simulation 4 8 1 3 3 Simulation value ...

Page 164: ... 2 Simulation process values 4 8 2 1 Enable simulation Description Select the process value s to be simulated Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Medi um temperature Default None selected Related Only if process values are marked in this parameter the setting of Simulated value under each relevant process value becomes relevant Path Maintenance an...

Page 165: ...0 000001 kg h Default 0 0 kg h Related Only if Mass flow is marked in Enable simulation then the setting of this parameter will be relevant The range and default setting are dependent on the selected Unit Path Maintenance and diagnostics Simulation Simulation process values Mass flow Simulation value 4 8 2 4 Flow velocity Simulation value Description Set the Flow velocity value to be simulated Set...

Page 166: ...ected Unit Path Maintenance and diagnostics Simulation Simulation process values Sound velocity Simulation value 4 8 2 6 Density Simulation value Description Set the Density value to be simulated Setting 0 0 kg m3 10000 0 kg m3 Default 1000 0 kg m3 Related Only if Density is marked in Enable simulation then the setting of this parameter will be relevant The range and default setting are dependent ...

Page 167: ...ty Simulation value 4 8 2 8 Medium temperature Simulation value Description Set the Medium temperature value to be simulated Setting 273 0 C 459 399994 F to 400 0 C 752 0 F Default 20 0 C 68 F Related Only if Medium temperature is marked in Enable simulation then the setting of this parameter will be relevant The range and default setting are dependent on the selected Unit Path Maintenance and dia...

Page 168: ... Various sensor alarms can be selected Default None selected Related This parameter is only available if Simulation mode is set to Simulate alarm ID number Path Maintenance and diagnostics Simulation Simulation alarms Alarms Sensor alarms 1 4 8 3 2 2 Sensor alarms 2 Description The simulation of single and multiple Sensor alarms 2 can be configured Setting Various sensor alarms can be selected Def...

Page 169: ...larms can be selected Default None selected Related This parameter is only available if Simulation mode is set to Simulate alarm ID number Path Maintenance and diagnostics Simulation Simulation alarms Alarms Process alarms 2 4 8 3 2 5 Process alarms 3 Description The simulation of single and multiple Process alarms 3 can be configured Setting Various process alarms can be selected Default None sel...

Page 170: ...ning limit Totalizer 1 below alarm limit Default None selected Related This parameter is only available if Simulation mode is set to Simulate alarm ID number Path Maintenance and diagnostics Simulation Simulation alarms Alarms Totalizer alarms 4 8 3 2 8 Input output alarms Description The simulation of single and multiple Input output alarms can be configured Setting Various input output alarms ca...

Page 171: ...ated can be configured The alarm status is activated on all outputs Setting Failure Function check Out of specification Maintenance required Default None selected Related This parameter can only be accessed if Status icons is set to NAMUR Path Maintenance and diagnostics Simulation Simulation alarms Alarm class 4 9 Audit trail 4 9 1 Parameter change log Displays list of logged parameter changes Lo...

Page 172: ... 20 logs can be listed with timestamp in the format YYYY MM DD hh mm Path Maintenance and diagnostics Audit trail Firmware update change log 4 9 4 Clear FW update change log expert Description The firmware update log can be reset using this parameter Setting Cancel Ok Default Cancel Related Path Maintenance and diagnostics Audit trail Clear FW update change log 4 10 Self test 4 10 1 Display test D...

Page 173: ...ined default values Setting Cancel Ok Default Cancel Related Path Maintenance and diagnostics Resets Set to default 4 11 2 Device restart write only Description Command to restart device Setting Cancel Ok Default Cancel Related Path Maintenance and diagnostics Resets Device restart 4 12 Firmware update Description The firmware of the device can be updated using a wizard Path Maintenance and diagno...

Page 174: ...Maintenance and diagnostics 4 12 Firmware update FST020 Function manual 172 Function Manual 09 2017 A5E42949526 AA ...

Page 175: ...ons Service channel USB USB mode 5 1 2 Auto mode Description The Auto mode can be enabled disabled When auto mode is enabled a device connected via a USB cable is always considered an MSD Setting Disabled Enabled Default Related Path Communications Service channel USB Auto mode 5 1 3 MSD connect write only Description This command is used to connect disconnect to a mass storage device for example ...

Page 176: ...lt Related Path Communication Modbus Channel 1 Slave address SW 5 2 2 Slave address HW read only Description The slave address HW is determined by the DIP switch setting on the transmitter cassette and can be read out in this parameter This address is used if the DIP switch is set to a value 0 Options Read only Related Path Communication Modbus Channel 1 Slave address HW 5 2 3 Baud rate Descriptio...

Page 177: ...escription The floating point number byte order used within the data filed of Modbus messages The first mentioned byte is the first byte sent Byte 3 corresponds to the left most byte MSB of a 32 bit floating byte number in big endian format byte 0 to the right most byte Setting 1 0 3 2 0 1 2 3 2 3 0 1 3 2 1 0 Default Related Path Communication Modbus Channel 1 Floating point byte order 5 2 6 Integ...

Page 178: ...t 0 Requested register 1 Target register 1 Bit 19 Requested register 20 Target register 20 Setting 0 to 1048575 Default Related Path Communication Modbus Channel 1 Register mapping Enable mapping 5 2 7 2 Source register 1 20 Description Modbus register that appears within Modbus request is redirected to the parameter specified by Target register 1 20 Setting Default Related Path Communication Modb...

Page 179: ...e t min t h t d US Pound lb s lb min lb h lb d Short ton STon min STon h STon d Ton long ton T h T d Custom unit Default kg h Related Path Communications Modbus Channel 1 Modbus units Mass flow unit 5 2 8 2 Volume flow unit Description Set the unit for volume flow values Setting Metric Litre l s l min l h l d Ml d hl s hl min hl h hl d m3 m3 s m3 min m3 h m3 d US Gallons Ugal s Ugal min Ugal h Uga...

Page 180: ...ic Meter m s m h US Foot ft s ft min Inch in s in min Custom unit Default m s Related Path Communications Modbus Channel 1 Modbus units Flow velocity unit 5 2 8 4 Sound velocity unit Description Set the unit for sound velocity values Setting Metric Meter m s m h US Foot ft s ft min Inch in s in min Custom unit Default m s Related Path Communications Modbus Channel 1 Modbus units Sound velocity uni...

Page 181: ...ns Modbus Channel 1 Modbus units Density unit 5 2 8 6 Kinematic viscosity unit Description Set the unit for kinematic viscosity values Setting cSt Default cSt Related Path Communications Modbus Channel 1 Modbus units Kinematic viscosity unit 5 2 8 7 Temperature units Description Set the unit for temperature values Setting C F R K Default C Related Path Communications Modbus Channel 1 Modbus units ...

Page 182: ...ic g kg t US lb STon T oz Custom unit Default kg is set to Mass flow Setting Metric Nl Nm3 Sl Sm3 US Sft3 Default Nl is set to Corrected volume flow Related Path Communications Modbus Channel 1 Modbus units Totalizer 1 unit 5 2 8 9 Service channel USB USB mode read only Description The USB mode can be read in this parameter Options USB communication Mass storage device MSD Related Path Communicati...

Page 183: ... Change user PIN code 6 2 Change expert PIN code expert Description The Change expert PIN code function can be accessed Setting Default Related Path Security Access management Change expert PIN code 6 3 Recovery ID Displays an ID number required to reset PIN if lost Record this ID number for use when contacting Siemens customer support Setting Default Related Path Security Access management Unique...

Page 184: ...control function can be configured Setting Disable Enable Default Enable Related Path Security Access management Enable access level control 6 6 Deactivate user PIN Description The Disable access level control function can be configured Setting Disable Enable Default Enable Related Path Security Access management Disable access level control 6 7 Auto logout Description The Auto logout function can...

Page 185: ... be be configured When the parameter is set to Off default you will not be prompted for password for 10 minutes after the last key press When the parameter is set to On you will be prompted to enter the password before each HMI operation Setting Off On Default Off Related Path Security Access management Auto logout 6 9 Logout Description The Logout function can be configured Setting Default Relate...

Page 186: ...Security 6 9 Logout FST020 Function manual 184 Function Manual 09 2017 A5E42949526 AA ...

Page 187: ...FST020 Function manual Function Manual 09 2017 A5E42949526 AA 185 Language 7 7 1 Language Description Select the local display language Setting English Deutsch Default English Related Language Language ...

Page 188: ...Language 7 1 Language FST020 Function manual 186 Function Manual 09 2017 A5E42949526 AA ...

Page 189: ... Support on the Internet In addition to our documentation we offer a comprehensive knowledge base online on the Internet at Service and support http www siemens com automation service support There you will find The latest product information FAQs downloads tips and tricks Our newsletter providing you with the latest information about your products Our bulletin board where users and specialists sh...

Page 190: ...Support A 1 Technical support FST020 Function manual 188 Function Manual 09 2017 A5E42949526 AA ...

Page 191: ... Hotline 187 I Inputs and outputs 62 Internet Contact person 187 Support 187 L Languages 185 P Paths 29 Pipe settings 19 Process values 38 Q Quick commissioning 17 Quick start wizards 13 S Sensor model 25 Sensor sizes 37 Sensor test blocks 37 Sensor diagnostics 141 Service 187 Service channel USB 173 180 Support 187 T Temperature monitoring 143 Totalizers 57 U User calibration 32 ...

Page 192: ...Index FST020 Function manual 190 Function Manual 09 2017 A5E42949526 AA ...

Page 193: ......

Page 194: ...rives Process Automation 76181 Karlsruhe GERMANY Subject to change without prior notice Order No A5E42949526 Lit No A5E42949526 AA Siemens AG 09 2017 www siemens com processautomation A5E35971532 For more information www siemens com flow ...

Reviews: