Extinguishing
Configuring the extinguishing terminal
16
388 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
16.7.2 'Action' elements
'Extinguishing terminal' – 'Keys' – 'Action' elements
The table below describes the configurable effects when the assigned button on
the extinguishing terminal is pressed. An 'Action' element represents a cause in
each case.
Designation
Description
'Reset warning panel'
Button resets the 'Illuminated warning panel'.
Prerequisite: The 'Illuminated warning panel' is in the 'Illuminated warning panel
resettable' state.
'LED test'
Button activates the 'LED test'. All of the visible lights on the extinguishing
terminal should light up when the button is pressed. Defective lights can be
identified in this way.
'Toggle main/reserve
cylinder bank (local sector
only)'
Button switches between the main extinguishing agent cylinders and the reserve
extinguishing agent cylinders.
'Toggle external equipment
mode'
Button switches between the different operation modes of the external equipment.
The button can, for example, switch between the 'On' and Off' modes of the
external equipment.
'Toggle alarm device mode' Button switches between the operation modes of the alarm devices in the flooding
zone.
'Toggle device supervision
mode'
The button globally disables monitoring for the following error messages by the
devices:
●
'Loss of agent'
●
'Incorrect position'
The isolation prevents the activation of the
intervention concept (IC) of the fire
control panel if necessary.
'Action' elements – parameters in the 'Overview' tab
The table below describes the parameters in the 'Overview' tab for a 'Action'
element:
Parameters
Value
Description
'Access level'
'1'
'2.2'
Defines the access level required to
perform the function of the button.