Extinguishing
Configuring flooding zone control
16
368 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
16.5.2 Effects functions
Activations and deactivations of controls are configured with 'Effects' functions. The
control effects are assigned to the corresponding outputs on the extinguishing
card. An 'Effects' function can be assigned up to eight outputs which trigger the
respective 'Effects' function.
Creating, assigning, and configuring 'Effects' functions
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
w
An 'Extinguishing sector control' element is created under the 'Extinguishing
control group' element.
1. Highlight the 'Actuator/valve' function in the 'Effects' zone.
2. Amend the customer text in the 'Overview' tab if necessary.
3. Configure the 'Actuator/valve' function in the 'Overview' tab.
4. Configure the error behavior of the 'Actuator/valve' function in the 'Details' tab.
5. Assign the associated output, to which the 'Actuator/valve' is connected, on the
extinguishing card to the 'Actuator/valve' function with 'Assign'. This is an
'Output/monitored' element.
6. Highlight the assigned element and enter the required customer text in the
'Overview' tab.
7. Configure the assigned element in the 'Hardware' tab. You will find information
about the individual parameters in chapter 'Configuring the extinguishing card
Alternatively, you can also configure the assigned element directly at the
relevant location in the 'Hardware tree'.
8. Highlight the 'Sounder' function in the 'Effects' zone.
9. Amend the customer text in the 'Overview' tab if necessary.
10. Configure the 'Sounder' function in the 'Overview' tab.
11. Configure the error behavior of the 'Sounder' function in the 'Details' tab.