14.7.2 Disabling switch-off and switch-on messages
In the standard setting, messages for switching logical channels off and on are
sent to connected
BACnet clients. These messages can be disabled.
Figure 153: Global BACnet settings
Disable switch-off and switch-on messages as follows:
1. Highlight 'Global BACnet configuration'.
2. Select the 'Details' tab in the detail editor.
3. Check the 'Suppress BACnet mode ‘OFF’ in channels' checkbox.
a
Switch-off and switch-on messages are disabled.
14.7.3 Delegating multiple alarms for 'Zones'
In the standard setting, the
pre-alarm and alarm messages are signaled on the
'Zones'. This leads to problems in the
BACnet model if it is in the 'Multiple alarms
per zone' setting.
Figure 154: Global BACnet settings
These BACnet messages can be delegated to the logical channels and replace the
messages for 'Activation' there.
Activate the 'Multiple alarms per zone on BACnet' as follows:
1. Highlight 'Global BACnet configuration'.
2. Select the 'Details' tab in the detail editor.
3. Check the 'Multiple alarms per zone on BACnet' checkbox.
a
'Multiple alarms per zone on BACnet' is activated.
14.7.4 Configuring BACnet client
The 'BACnet client configuration' element must be created in the tree view of the
'Network' task card so that the
BACnet client can be configured.
management stations or third-party devices that are
accepted by the FS720 system. The customer text of this element is also used in
the event memory to log all actions triggered by a management station.
A BACnet client is identified by the 'BACnet device ID'.