'Control' task card
Extinguishing standard interface SST [DE]
12
242 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Configuring LED 2 for the 'Timeout/Fault/Unexpectedly
open/Unexpectedly closed' damper state
1. Select 'LED/output | 2' and assign the LED as follows:
– Go to the left of the 'New cause dialog' and select the 'All faults' event
under 'Events 'Fault''.
– On the right-hand side, select the same 'Fire damper output/supervised' as
for the first assignment from the control tree: 'Control tree' > 'Station' >
'Damper control group' > 'Fire damper control' > 'Effects' > 'Fire damper
output/supervised'.
– Click on 'Assign'.
2. Select the cause element that has been created under 'LED/output | 1' and set
the following properties on the 'Overview' tab:
– Colour: 'Yellow'
– Priority: '03'
– LED mode: 'Inactive: Off / active: On'
12.7 Extinguishing standard interface SST [DE]
The extinguishing standard interface SST is used for the control and indication of
the extinguishing activation of a third party extinguishing control installation. The
input/output module FDCIO224, which is integrated in the fire control panel, is used
as an interface between the fire control panel and the extinguishing control
installation. The inputs of the fire control panel for the extinguishing control
equipment are monitored for short-circuit and open line.
The following events are evaluated by the extinguishing control system via the
inputs of the input/output module:
●
'Input 'Discharged''
●
'Fault extinguish.'
Extinguishing is activated via an output of the input/output module.