Periphery board (2 loops) FCI2002-A1
7
Pin assignments
53
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Element
Des.
Function
LEDs
H1
Power Down Ready
H201
Display FDnet module 2
H401
Monitoring supply output 1 (fuse F401)
H402
Monitoring supply output 2 (fuse F402)
H501
Monitoring alarm output (fuse F501)
H601
Monitoring fault output (fuse F601)
H100-
H115
Indications of programmable inputs and outputs
Fuses
F400
Horn output (1 A/T); Schurter OMT 125
F401
Supply output 1 (1 A/T); Schurter OMT 125
F402
Supply output 2 (1 A/T); Schurter OMT 125
F501
Monitored alarm output (1 A/T); Schurter OMT 125
F601
Monitored fault output (1 A/T); Schurter OMT 125
Adjustment elements
S100
Switchover of the LED indicators for the inputs and outputs
7.3
Pin assignments
Inputs and outputs which are not used do not require termination.
FDnet detector lines which are not used must not be terminated.
7.3.1
X12 detector line loop 2
Pin
Designation
Description
4
LOOP2_2–
Loop 2 / stub 4 (–)
3
Loop 2 / stub 4 (+)
2
LOOP2_1–
Loop 2 / stub 3 (–)
1
Loop 2 / stub 3 (+)
Admissible cable cross-section: 0.2…1.5 mm²
-
3
4
+
-
1
2
X12
LOOP2_1-
LOOP2_2-
+
One loop or two stubs can be connected.