6
Fire terminal board FTI2001-A1
Adjustment elements
50
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
6.5
Adjustment elements
Switch
Function
Position Meaning
S1-1
Supply input 1 'VSYS1'
ON
Input is not used (default setting)
OFF
Input is used (monitored)
S1-2
Supply input 2 'VSYS2'
ON
Input is not used (default setting)
OFF
Input is used (monitored)
6.6
Technical data
Supply
Designation
'VSYS+'; 'VSYS-'
(connector X1)
Operating voltage
DC 21…28.6 V (= Usys)
Operating current
Max. 2.5 A
Input 3rd supply source
Designation
'3SRC+'; '3SRC-'
(connector X1)
Voltage
DC 7…30 V
Current
Max. 40 mA
Power supply input 1
Designation
'VSYS +1', 'VSYS -1'
(connector X7)
Voltage
DC 21…28.6 V (= Usys)
Current
Max. 2 A
Power supply input 2
Designation
'VSYS +2', 'VSYS -2'
(connector X6)
Voltage
DC 21…28.6 V (= Usys)
Current
Max. 2 A
Supply output
Designation
'VSYS 1', 'VSYS 2'; 'GND 1', 'GND 2'
(connector X5)
Voltage
DC 21…28.6 V
Current
Max. 1 A per output
Connection terminals
Inputs and outputs:
Design
Spring clips
Admissible cable cross-section
0.2…2.5 mm²
Mechanical data
Dimensions (L x W x H)
210 x 150 x 40 mm
Weight
130 g