48
RT interface FCI2006-C1 [CH]
Technical data
298
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Settings
NO = wire jumper or resistor across solder pins Y3
NC = wire jumper or resistor across solder pins X3
Settings for Switzerland (default)
Relay
Pin no.
Solder pins
NO/NC
Resistance
K1
13
Y3
NO
Open
X3
NC
Bridged
K2
15
Y4
NO
Open
X4
NC
Bridged
K3
17
Y5
NO
Open
X5
NC
Bridged
K4
19
Y6
NO
Open
X6
NC
Bridged
Alarm
8
Y1
NO
Bridged
X1
NC
Open
Fault
10
Y2
NO
Bridged
X2
NC
Open
48.6
Technical data
Supply input
Supply voltage
DC 20…32 V
Quiescent current
0 mA at DC 24 V
Maximum current
100 mA
Relay 1…4
Designation
'K1'…'K4'
Design
4 x pole reversal
Operating current/relay
Max. 12 mA
DC switching voltage
Max. DC 30 V
DC switching current
Max. 5 A
LEDs
Status display relay and test
Lights up when relay is switched
Connection terminal X15
Design
Printed circuit board plug connector and
terminal strip on card cage
Wieland 20-pin type 99.264.9700.2
Admissible cable cross-section
0.14…2.5 mm
2
Mechanical data
Card E3G091
Card dimensions (W x H x D)
100 x 100 x 15 mm
Card weight
58 g
FCI2006-C1 set
Set dimensions (W x H x D)
222 x 243 x 80 mm
Set weight
1.41 kg