Configuring the line tester
The FDUL221 line tester must be set to the relevant protocol if it is being used on a
detector line. The protocol is permanently set in the 'EL' operation mode and
cannot be configured.
Control panel
Protocol
Mode: FDnet
FC20xx
FDnet
32 V
FC72x
C-NET
32 V
CS114x
FDnet
32 V
SIGMASYS
FDnet
SIGMA
_
FDnet/C-NET
Spy
To configure, proceed as follows:
The FDUL221 line tester is switched off.
1. Hold down the button and switch the FDUL221 line tester on with the
switch.
The FDUL221 line tester is in the 'Configuration' menu tree.
2. Select 'Mode: FDnet …' using the
buttons.
3. Select the required protocol with the button.
4. Select further sub menus or a function with the
buttons.
5. Further changes in the sub menu or function can be made in the same way.
6. To quit a sub menu or a function, press the button.
7. To quit 'Configuration', select 'Save & Exit' or 'Exit'.
The FDUL221 line tester switches to the 'Topology' menu tree.