Structure and function
Setup
3
28 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
Technical CO alarm
The detector has a high-quality CO sensor which is based on the measurement
principle of the electro-chemical cell.
Instances of the specified CO concentration being exceeded can be detected by
the CO sensor. The limit values vary depending on the parameters set.
You can set the following CO response behaviors on the neural fire detector
FDOOTC241:
Static CO alarm thresholds
Dynamic CO alarm thresholds
The response behavior is configured with the 'SintesoWorks' software or on the
control panel's Person Machine Interface.
Technical Ambient Supervision Message
'Technical Ambient Supervision Message' mode detects an increase in
temperature or CO concentration caused by hysteresis above a specified
threshold.
Temperature monitoring compares the current measured temperature with a preset
threshold value.
CO monitoring compares the current measured CO concentration with a preset
threshold value.
You can set the following parameters on the neural fire detector FDOOTC241:
CO concentration or temperature threshold value
Alarming when the temperature threshold value is exceeded or undershot
Alarming when the CO concentration threshold value is exceeded
Hysteresis range
The 'Technical Ambient Supervision Message' is configured on the control panel
using the 'SintesoWorks' software.