3.3 Function
3.3.1 Danger levels
The manual call point can transmit the following danger levels to the control panel:
Danger level
Meaning
0
Normal state, no danger
3
Alarm
The evaluation of the danger level and the resulting measures (e.g. activation of
remote transmission) are configured on the control panel.
3.3.2 Internal alarm indicator
The LED indicator of the alarm indicator has the following meanings:
LED indication
Meaning
Off
●
Normal condition
Green
Flashes once per second
●
Test mode is active
Red
Flashes once per second
●
Localization is active
o r
●
Alarm is triggered
Red and green alternating
Flashes twice per second
●
Alarm is triggered/localization is active
a n d
●
Test mode is active
See also
2
3.3.3 Line separator
All FDnet/C-NET devices are equipped with a line separator.
The FDnet/C-NET device is equipped with electronic switches which isolate the
defective part in case of a short-circuit on the FDnet/C-NET detector line. The rest
of the detector line remains serviceable. On a loop line, all FDnet/C-NET devices
remain fully functional after a single short-circuit.
3.3.4 Test mode
A test mode must be set on the control panel to test the manual call points. When
in test mode, alarms from the manual call points are not forwarded by the control
panel.
See also
2
Structure and function
Function
3