Specifications
Technical data
8
28 | 32
007063_h_en_--
8 Specifications
8.1 Technical data
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
●
Document 007065
Detector line
Operating voltage
DC 12…33 V
Operating current (quiescent)
250 µA
Maximum current connection factor
1
Quiescent current connection factor
1
Address connection factor
1
Separator connector factor
1
Protocol
FDnet/C-NET
Compatibility
See 'List of compatibility'
Line separator
Line voltage:
●
Nominal
DC 32 V (= V
nom
)
●
Minimum
DC 12 V (= V
min
)
●
Maximum
DC 33 V (= V
max
)
Voltage at which the line separator opens:
●
Minimum
DC 7.5 V (= V
SO min
)
●
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches are
closed
Max. 1.5 A (= I
C max
)
Switching current (e.g., in the event of a
short-circuit)
Max. 2 A (= I
S max
)
Leakage current when switches are open Max. 1 mA (= I
L max
)
Serial impedance when switches are
closed
Max. 0.4
Ω
(= Z
C max
)
When operated on the FDnet/C-NET, the line separator is closed via an actuation
signal from the control panel. Required line voltage: DC 12...33 V (normal range)
External alarm indicators
Number of external alarm indicators that
can be connected
None
Connections
Detector line:
●
Design
Strands 500 mm long with pressed-
on 2.8 x 0.8 mm flat connector
sleeves
●
Cable cross section
0.5 mm
2