Planning
Accessories
4
007063_h_en_--
19 | 32
Rules for the branching of a sub-stub from a loop
●
Only one sub-stub is permitted between two FDnet/C-NET devices.
●
One sub-stub is permitted at the start and end of the loop respectively,
between the connection terminals of the fire control panel and the first line
device.
●
If there is more than one stub between two FDnet/C-NET devices, a line
separator must be fitted between the stubs.
The following figures show the common variants of a modernized detector line on
which the FDnet/C-NET devices (T) are installed with integrated line separation
function. The outgoing stub lines A to D are connected to the FDCL221 line
separators via terminal blocks or micro terminals (X).
Figure 5: Housing FDCL221 line separator in intermediate distributors
1 Intermediate distributor
C Sub-stub C
2 FDnet/C-NET loop
D Sub-stub D
3 Line separator FDCL221
T FDnet/C-NET device
A Sub-stub A
X Terminal blocks or micro terminals
B Sub-stub B