5
Mounting / Installation
Installation
70
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
5.3.8
'PreAlarm' relay output for pre-alarm
Relay output for 'pre-alarm' alarm level.
Connection: n.o. (default setting)
Properties
Activation occurs according to the chosen setting.
The connection can be changed to 'n.c.' with the '
FXS2051
ASD Configuration
Tool' software. The chosen setting applies automatically to 'Inspect', 'Prealarm',
'Fire 1', 'Fire 2'.
5.3.9
'Fire 1' relay output for fire alarm 1
Relay output for alerting the fire brigade.
Connection: n.o. (default setting)
Properties
Activation occurs according to the chosen setting.
The connection can be changed to 'n.c.' with the '
FXS2051
ASD Configuration
Tool' software. The chosen setting applies automatically to 'Inspect', 'Prealarm',
'Fire 1', 'Fire 2'.
5.3.10
'Fire 2' relay output for fire alarm 2
Relay output for alarm level 2 to activate external extinguishing equipment.
Connection: n.o.
Properties
Activation occurs according to the chosen setting.
The connection can be changed to 'n.c.' with the '
FXS2051
ASD Configuration
Tool' software. The chosen setting applies automatically to 'Inspect', 'Prealarm',
'Fire 1', 'Fire 2'.