5
Mounting / Installation
Installation
66
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
5.3.2
'Smoke 4…20 mA' analog output
Configurable 4…20 mA analog output.
The setting is made in the 'Current loop' menu with the '
FXS2051
ASD
Configuration Tool' software for one of the following values:
Smoke value (device default)
Dust value (FDA241 only)
Airflow (FDA241 only)
Fine dust value (FDA241 only)
Example illustrating analog input (IN)
Connection for DC 9…25 V power supply
Smoke value (device default)
4…20 mA analog output
No smoke
4 mA
Inspect
8 mA
Prealarm
12 mA
Fire 1
16 mA
Fire 2
20 mA
Airflow
4…20 mA analog output
0 l/min
4 mA
20 l/min
8 mA
40 l/min
12 mA
60 l/min
16 mA
80 l/min
20 mA